Technical User Guide
7
DOL 530/DOL 630 Extension Box
3
Electrical connection
Qualified personnel must perform installation, service and fault-finding of all electrical
equipment in accordance with the applicable national and international standard EN 60204-1 and
any other EU standards that are applicable in Europe.
The installation of a power supply isolator is required for each motor and power supply to
facilitate voltage-free work on the electrical equipment. SKOV A/S does not supply the power
supply isolator.
3.1
Extension box with two I/O modules (136471)
1)
Connect flat cable plug from
I/O module 1
in house controller to
I/O module 2
in the extension
box
(A)
.
2)
Connect flat cable plug from
I/O module 2
to
I/O module 3
in the extension box
(B)
.
3)
Set jumper OFF/ON
(C)
on the
I/O module 1
of the house controller to OFF.
4)
Set jumper OFF/ON
(D)
on the
I/O module 2
of the extension box to OFF.
5)
Set jumper OFF/ON
(E)
on the
I/O module 3
of the extension box to ON.
6)
Set the I/O-modules address switch (Rotary Switch) as follows:
I/O module 1
Adresse =
1
I/O module 2
Adresse =
2
I/O module 3
Adresse =
3
7)
Connect the earthing contact of the extension box
(F)
to the earthing contact of the house controller
(G)
.
8)
Run the earth cable through the lower rubber sleeve
(H)
.
9)
Set CAN protocol jumper
(I)
according to the setting on the main module. If jumper does not exist
on the main module, set CAN protocol jumper on the I/O module to Classic.
0
2
1
34567
8
9
A
BCD
EF
House controller
Extension box