DOL 434 LPV
32
Technical Manual
Test the relay-controlled light by connecting and disconnecting
the relay.
Activate and check that the light is on.
Deactivate and check that the light is off.
Test the light dimmer by increasing and dimming the light inten-
sity.
Set the Light dimmer requirement to maximum.
Set to medium and check that the light is dimmed in the house.
Set the Light dimmer requirement to 0 and check that the light
is off in the house.
5.2.2.2 Testing water meter
Select the menu
Technical | Manual/auto.
Then select
Production | Water| Water meter relay
and activate
Manual mode
.
Activate and deactivate the water meter relay.
Check that the solenoid valve changes.
Read whether the values change to check for connection to the
water meters.
5.2.2.3 Testing relay for 24-hour clock
Select the menu
Technical | Manual/auto.
Then select
Production | 24-hour clock
and activate
Manual mode
.
Activate the testing and check that the 24-hour clock is on.
Deactivate the testing and check that the 24-hour clock is off.