DOL 31 Speed Controller
24
Technical User Guide
7.9.2 Set turn off limit
NOTE: The function is only active in Automatic Slave mode.
The function is applied if there is a requirement for the DOL 31 output to be cut off completely at a certain volt-
age on the analog control signal (turn off limit).
If the turn off limit is set to 0 V, the function is inactive and the DOL 31 output will remain at minimum (not in-
verted) or maximum (inverted).
Turn off
No
0.5 V
Turn off limit
Not inverted
Relative voltage between
0 – 2 V.
Inverted
Relative voltage between
8 – 10 V.
7.10 Contrast
Adjust contrast in display.
Contrast
60 %
7.11 Backlight
Adjust backlight.
Backlight
30 %
7.12 Language
Choose between Danish, English, German, Finnish, Swedish, Polish, Russian, Estonian, and Spanish.
Language
English
7.13 Version Information
Information about hardware configuration and software version.
Version
Software 1.3
Serial no. 1 xxxx
Serial no. 2 xxxx