CE Installation Guide
CE Installation Drawings
5- 2
SKF Machine Condition Transmitter
User
Manual
connecting a system common bus-bar located in the
system enclosure to the enclosure system ground bus
bar.
Each sensor/transducer providing input to the system
should be connected to its respective transmitter/monitor
via a twisted-shielded cable assembly approved by the
manufacturer for use with that specific sensor/transducer
type. The sensor cable-shield must be connected to
system ground at one end only. When the
sensor/transducer case is mounted on an earth grounded
machine casing or structural point, the cable shield may
be terminated at the sensor end. Otherwise it should be
terminated to earth-ground at the transmitter/monitor
end via direct connection to the system ground bus bar.
Signal outputs (4-20 mA) intended for connection to
remote loads, should be connected using manufacturer
approved, twisted-shielded-pair cable. If the remote load
is referenced to earth-ground at a location different from
that of the system enclosure, a current-loop isolator may
be required.
CE Installation Drawings
MCT (+24 Vdc Power Supply Installation)
Summary of Contents for CMSS500 Series
Page 8: ......
Page 17: ...Introduction Identification Label SKF Machine Condition Transmitter 1 7 User Manual...
Page 38: ...CMSS500 Series Transmitters Output 2 18 SKF Machine Condition Transmitter User Manual...
Page 61: ...CE Installation Guide CE Installation SKF Machine Condition Transmitter 5 5 User Manual...
Page 62: ...CE Installation Guide CE Installation 5 6 SKF Machine Condition Transmitter User Manual...
Page 66: ...Mounting and Outline CMSS500 A 4 SKF Machine Condition Transmitter User Manual...