CMSS500 Series Transmitters
Output
SKF Machine Condition Transmitter
2- 17
User Manual
C
deg
27
.
34
C
deg
138.8
mA
16
6.05mA
-
mA
10
Celsius
in
Reading
Output
Converted
=
×
=
Buffered Output
The MCT provides access to the buffered transducer
signal using a BNC connector on the front of the unit and
on a screw terminal at the top of the unit. These
buffered outputs have the same sensitivities, units, and
bias voltages as the transducer itself (i.e., mV/g for an
accelerometer or mV/IPS for a velocity transducer). This
output can be connected to portable monitoring
equipment or analyzers (i.e., SKF Microlog
®
Series Data
Collector / Analyzer), or can be used to check the bias
output voltage (BOV) of low-impedance transducers using
a digital voltmeter. The buffered output is unfiltered.
For electro-mechanical velocity transducers only: The
buffered output sensitivity is scaled to 100 mV/IPS,
regardless of the actual input sensitivity. For example, a
145 mV/IPS transducer will have a scaled buffered
output sensitivity of 100 mV/IPS.