20
SPECIFICATIONS
Table 7. Line Mode Specifications
MODEL
PL201~12KW
Rated power
1 ~ 12KW(230VAC)
1 ~ 6KW(120VAC)
Input Voltage Waveform
Sine wave(Utility or Generator)
Nominal Input Voltage
230Vac
120Vac
Low Line Disconnect
184Vac±4%(NOR)
85Vac±4%(NOR)
135Vac±4%(WID)
80Vac±4%(WID)
Low Line Re-connect
194Vac±4%(NOR)
95Vac±4%(NOR)
145Vac±4%(WID)
85Vac±4%(WID)
Note: 1.NOR setting can be used for general electrical appliance
2. WID setting can be used only for some special load,
Such as lamp, fan.
High Line Disconnect
263Vac±4%(NOR)
136Vac±4%(NOR)
263Vac±4%(WID)
140Vac±4%(WID)
High Line Re-connect
253Vac±4%(NOR)
131Vac±4%(NOR)
253Vac±4%(WID)
135Vac±4%(WID)
Max AC Input Voltage
270VAC
150VAC
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Low Line Frequency Disconnect
40+0.3Hz for 50Hz, 50+0.3Hz for 60Hz
Low Line Frequency Re-connect
41+0.3Hz for 50Hz, 51+0.3Hz for 60Hz
High Line Frequency Disconnect
55+0.3Hz for 50Hz, 65+0.3Hz for 60Hz
High Line Frequency Re-connect
54+0.3Hz for 50Hz, 64+0.3Hz for 60Hz
Output Voltage Waveform
As same as Input Waveform
Output Short Circuit Protection
Air switch
Efficiency (Line Mode)
>97%
Transfer Time
15ms (typical) 20ms max(WID)
Bypass charger enable in off mode
Yes
Note: NOR – Normal range; WID-Wide range