USER MANUAL

PL20 Series Hybrid Inverter

Summary of Contents for PL20 1.5KW

Page 1: ...USER MANUAL PL20 Series Hybrid Inverter ...

Page 2: ...7 AC Connections 7 Machine panel introduction 9 OPERATION 11 Front Panel and Configuration Switch 11 Setting Indicators 12 LCD display meaning 17 Table 5 display meaning 17 Operating Indicators 18 Table 6 Fault code meaning 19 SPECIFICATIONS 20 Table 7 Line Mode Specifications 20 Table 8 Invert Mode Specifications 21 Table 9 AC Charger Mode Specifications 22 Table 10 Solar Charger Mode Specificati...

Page 3: ...red Incorrect re assembly may result in a risk of electric shock or fire 5 To reduce risk of electric shock disconnect all wiring before attempting any maintenance or cleaning Turning off the unit will not reduce this risk 6 CAUTION Battery are not already installed by the supplier only a qualified professional e g service person may install the Inverter 7 WARNING WORKING IN VICINITY OF A LEAD ACI...

Page 4: ...one should be within range of your voice to come to your aid when you work near batteries 2 Have plenty of fresh water and soap nearby in case battery acid contacts skin clothing or eyes 3 Wear complete eye protection and clothing protection Avoid touching eyes while working near batteries Wash your hands when done 4 If battery acid contacts skin or clothing wash immediately with soap and water If...

Page 5: ...ds The input power of PL20 Series hybrid Inverter comes from PV system and AC grid which not only supply power to AC loads but also charge the battery bank when the power from AC grid or AC generator is present also known as Line Mode In the event of AC grid or AC generator outage the AC loads can be alternatively powered by PV system if the illumination is sufficient and battery bank The followin...

Page 6: ...ed lead acid or sealed GEL AGM lead acid batteries so ensure that your batteries are in one of these categories PL20 inverter with built in MPPT solar controller for the battery and solar panel connection please refer to figure 2 figure3 and figure4 If with the built in 48 MPPT 40A solar charge controller then please configure solar panels more than 2350W otherwise it can not reach the maximum cha...

Page 7: ...5 Figure 3 PL20 24V solar inverter system the connection diagram of solar panel and battery Figure 4 PL20 48V solar inverter system the connection diagram of solar panel and battery ...

Page 8: ... used and must be rated for DC operation Do not use devices rated only for AC service they will not function properly Note that some installation requirements may not require a disconnect device although over current protection is still required Battery Cable Connection Observe Battery Polarity Place the ring terminal of DC cable over the bolt and directly against the unit s battery terminal Tight...

Page 9: ...0 Nm PL20 6KW 230Vac PL20 3KW 110Vac 50A 10AWG 12AWG 1 5 2 0 Nm PL20 8KW 230Vac PL20 4KW 110Vac 60A 10AWG 10 AWG 2 0 2 5 Nm PL20 10KW 230Vac PL20 5KW 110Vac 70A 8AWG 10 AWG 2 0 2 5 Nm PL20 12KW 230Vac PL20 6KW 110Vac 80A 6AWG 8AWG 2 0 2 5 Nm AC Connections Installation should be done by a qualified electrician Consult local code for the proper wire sizes connectors and conduit requirements On the ...

Page 10: ...ompartment as figure 5 connect the GND green yellow Line brown and neutral blue wires from the AC input utility generator etc to the terminal block Caution Be sure that AC source is disconnected before attempting to hardwire it to the unit Step 3 Connect the AC Line output wiring to the terminal marked AC Line output following the wiring guide inside the compartment Torque the wires into the termi...

Page 11: ...9 Machine panel introduction Figure 6 PL201 3KW Front panel Figure 7 PL201 3KW Back panel Figure 8 PL204 6KW Front panel ...

Page 12: ...10 Figure 9 PL204 6KW Back panel Figure 10 PL208 12KW Front panel Figure 11 PL208 12KW Back panel ...

Page 13: ...n to enter the setting interface can be used for selecting different contents Voltage frequency charging current Up SELECT Up SELECT button can be used for selecting parameter on the function setting mode Down SELECT Down SELECT button can be used for selecting parameter on the function setting mode ENTER Confirm data save function ...

Page 14: ...uration option 1 Input voltage range Setting Narrow range mode Wide range mode NO Description Selectable option 1 Input voltage setting Wide Normal 2 Output voltage setting 208 220 230 240Vac 3 Output frequency setting 50 60Hz Automatic 4 AC charge on off AC charge on AC charge off 5 AC Charger current setting 20A 35A 50A 70A 90A 6 DC AC Intelligent mode selection setting DC mode priority AC mode ...

Page 15: ... 2 Output voltage Setting 208Vac 220Vac 230Vac 240Vac four kinds of output voltage can be set 3 Output frequency Setting 50 60Hz frequency output can be adjusted as well as the adaptive AC input frequency ...

Page 16: ...ded into 5 different stall for adjusting 20A charger can be adjusted into 4A 8A 12A 16A 20A 35A charger can be adjusted into 7A 14A 21 28A 35A 50A charger can be adjusted into 10A 20A 30A 40A 50A 70A charger can be adjusted into 14A 28A 42A 56A 70A 90A charger can be adjusted into 18A 36A 54A 72A 90A ...

Page 17: ...15 6 DC AC Intelligent mode selection setting AC mode priority DC mode priority 7 Battery capacity setting ...

Page 18: ...16 11 kinds of battery capacity settings 65AH 80AH 100AH 150AH 200AH 250AH 300AH 400AH 500AH 600AH 800AH ...

Page 19: ...n every 3s Display AC output voltage and frequency will change to the other info in every 3s Working mode and fault code Battery indicator Battery capacity segment will lighting to comply with battery voltage Battery voltage 26V 25V 26V 24V 25V 23V 24V 21 6V 23V 20V 21 6V 20V ALARM 1beep 2s continue Load indicator The load indicate the load percentage comply with load VA or W show the bigger value...

Page 20: ... the inverter and battery indicator light PV DC Mode PV charging battery battery invert output PV and battery mode indicator light AC PV mode AC input and PV charging battery indicator light PV Mode Inverter without work PV charging battery PV and battery mode indicator light Fault Mode Inverter fault fault indicator light and buzzer alarming ...

Page 21: ...th manufacture F04 Over temperature alarm light on Inverter operate environment is very bad insufficient ventilation and indoor temperature is very high Close the inverter and wait for 10 minutes after inverter cool start again F05 Low battery voltage alarm light on Battery damage Battery deeply discharged so need to charge again battery problem please replaces the battery Inverter charger no work...

Page 22: ... 4 NOR 136Vac 4 NOR 263Vac 4 WID 140Vac 4 WID High Line Re connect 253Vac 4 NOR 131Vac 4 NOR 253Vac 4 WID 135Vac 4 WID Max AC Input Voltage 270VAC 150VAC Nominal Input Frequency 50Hz 60Hz Auto detection Low Line Frequency Disconnect 40 0 3Hz for 50Hz 50 0 3Hz for 60Hz Low Line Frequency Re connect 41 0 3Hz for 50Hz 51 0 3Hz for 60Hz High Line Frequency Disconnect 55 0 3Hz for 50Hz 65 0 3Hz for 60H...

Page 23: ... and Fault after 60s Load 150 beeps 0 5s every 1s and Fault after 20s Capable of starting electric motor YES Output Short Circuit Protection Current limit Fault after 10s Air switch Power saver Load 25 5W Enabled on P S auto setting of Remote control DC voltage Nominal DC Input Voltage 12VDC 24VDC 48VDC Min DC start voltage 10 5Vdc 21Vdc 42Vdc Low DC Alarm 10 5Vdc 0 2Vdc 21Vdc 0 4Vdc 42 0 0 8Vdc L...

Page 24: ...arge Protection Bat V 15 5Vdc Fault Buzzer alarm for 12Vdc Bat V 31 0Vdc Fault Buzzer alarm for 24Vdc Bat V 61 0Vdc Fault Buzzer alarm for 48Vdc beeps 0 5s every 1s fault after 60s Charge Algorithm Three stage Boost CC constant current stage Boost CV constant voltage stage Float constant voltage stage Note NOR Normal range WID Wide range Table 10 Solar Charger Mode Specifications Rated Battery vol...

Page 25: ...g Earthing ABYC standard Follow customer requirement Inverter mode the neutral and the earth joined Line mode the neutral and the earth separated Use a Relay to realize the function Audible Noise 65dB max Cooling Forced air variable speed fan Size L W H mm 482 5 336 5 189 5 517 5 396 5 189 5 627 5 416 5 204 5 MODEL 1K 1 5K 2K 3K 4K 5K 6K 8K 10K 12K Net weight Kg 22 0 23 0 24 0 28 0 30 5 35 5 38 5 ...

Page 26: ...arger than the max capacity of solar battery charger 900W for 3000VA model and 2600W for 5000VA model Surplus capacity of PV string does not help the solar charger s capacity and only result in higher installation cost Total Vmp of the string shall be within the operating voltage range of solar battery charger 60 72V for 3000VA model and 120 144V for 5000VA model are recommended Total Imp of the s...

Page 27: ...x 8 89A 17 78A 20A Max PV Input Current OK Example 2 How to connect 5000VA model to PV panels with the following parameters Pmax 260W Voc 37 7V Isc 8 89A Vmp 30 9V Imp 8 42A 1 The max PV input power for 5000VA model is 2600W 2600W 260W 10 min 10 PV panels shall be connected 2 Best Operating Voltage Range is 110 144V 144V 30 9V 4 66 max number of PV panel in series is 4 3 Max input charging current...

Page 28: ...urrent OK DISPOSAL In the event the product reaches the end of its service life please contact the local dealer for disposal instructions The product must not be disposed of with the household waste Disposal of the product at the end of its service life shall be done in accordance with applicable disposal regulations for electronic waste Version 00 614 00020 00 ...