background image

 

 

 

Interface 
type   

 

port D1 

 port D3 

S3-1  S3-2  S3-3  S3-4 

RS-485 2-w. 

RS-485 4-w. 

RS-422 

Table  2.  Choosing  RS-485  interface  types 

using dip switch bank S3 

 

Two-wire  RS-485  mode  uses  the  input  terminals  for 
I/O. In older ADS/VAD units, for two-wire  mode the 
+ in and + out needed to be combined, as well as  - in 
and - out; old and new units can be used together with 
the old-style cable layout. 

 
Current  loop  output:

  The  RS-485  output  impedance 

of  port  D1  can  be  made  suitable  for  digital  20  mA 
current  loop  ('TTY')  applications  by  pulling  a  2-pin 
jumper (C2-3) from the board, thus inserting a resistor 
into  the  non-inverting  data  line.  The  jumper  may  be 
put  on  pins  C1-2  to  save  it.

  Current  loop  I/O  should 

use  only  non-inverting  lines  and  signal  ground  (see 
figure  3);  the  interface  type  should  be  set  to  RS-485 

(4-w).  Input  signal  voltage  on  A-GND  (IN+-GND) 
should be at least 4V. 

 

RS-485  line  biasing:

  In  most  cases,  the  RS-485  data 

interface  works  with the default settings. If, however, 
data  line  biasing  is  called  for  by  other  equipment 
connected to the  ADS 1200, biasing impedances  may 
need to be applied and dwell times set. With the other 
dip  switches  configured  for  RS-485  mode,  the 
eightfold  switch  banks  S1  (for  interface  D1)  and  S2 
(for  interface  D3)  on  the  ADS  1200  circuit  boards 

(figure 2) control attachment of two bias impedance 
resistors  to  both  input  and  inverting  input  (table  3 
below).  

 

Switch 

bank S1 for D1 
bank S2 for D3 

Function (RS-485 mode set) 

1-3 

dwell time select, see table 4 

4 ON 

inverting input tied to +5V over 390 

 

5 ON 

inverting input tied to +5V over 10 k

 

6 ON 

line termination 120 

 (default = off) 

7 ON 

input tied to GND over 10 k

 

8 ON 

input tied to GND over 390 

 

Table  3.  Choosing  bias  resistances,  dwell  times and  line 
termination for interfaces D1 and D3 

 

Note  that  the  'soft  zero'  biasing  adaptation  method 
used  ties  the 

inverting

  ('negative')  input  to  the 

higher  voltage,  while  the  biasing  resistor  of  the 
normal input is tied to signal ground. This provides 
a well-defined bus state when no driver is active.

 

The first three dip switches of the banks S1 and S2 
on  the  circuit  boards  (figure  3)  are  used  to 
configure  the  tristate-sensing/dwell  timing  of 
interface  D1  and  D3,  respectively,  if  biasing  of 
RS-485  lines  is  used,  to  help  indicate  the 
conclusion  of  transmission  (table  3).  Dwell  time  is 
approximately 10*bit length or slightly longer. 

 

 

Setting 

no. 

Switch 

bank S1 for D1 
bank S2 for D3

 

Dwell 

time 

(±7%) 

Data 

rate 

(bit/s)

 

 

 

OFF  OFF  OFF 

0-max 

OFF  OFF 

ON 

** 

0-max 

OFF 

ON 

OFF 

0.17 ms 

64000 

OFF 

ON 

ON 

0.34 ms 

38400 

ON 

OFF  OFF 

0.67 ms 

19200 

ON 

OFF 

ON 

1.35 ms 

9600 

ON 

ON 

OFF 

2.68 ms 

4800 

ON 

ON 

ON 

5.38 ms 

2400 

 
*)   default, hardware tri-state detect (1V differential sense, 

not to be used together with line-biasing

**) logic high in the data directly drives the output enable 

(i.e. no delay). This setting is especially suitable for 
very low data rates.  

 

Table 4. Dip switch settings for unbiased and biased 

RS-485 interfacing. Settings 1-7 all need bias resistors 
to define zero. 

 

Depending  on  the  actual  data  rate,  switches  1-3  of 
block  S1  and  S2  should  then  be  set  as  per  table  4 
(

read the notes below

). Default is all three switches 

off, i.e. hardware tristate sensing. 

 
Notes on dwell times:

 

When in doubt about which of two dwell times to 

select, use the longer of the two.

 

- Settings 1-7 only work if the lines are biased to a 
‘soft zero’. 
- The serial receiver dwell timing circuitry (re)starts 
a  timer  on  the  rising  edges  of  input  data  from  the 
copper  side,  at  the  same  time  sending  an  output 

Figure 3. Current loop connections 

U603

1

1

ON

S1

S2

S3

1
2
3

1
2
3

1
2
3

A

B

C

ADS TRX 650 2033 3

WWJJ

1

Figure 2. ADS TRA/B printed circuit board; details left out 

for clarity. 

Take care not to damage the optical fiber 

floating above the board.

 

 

GND

 

B (IN-)

 

A (IN+)

 

GND

 

B (OUT-)

 

A (OUT+)

 

220 ohm,

 

internal

 

jumper removed

 

Reviews: