16
4 Technical Data
Technical parameters table (400KW)
Specification
PDC-400K
LV PV input mode (Default)
HV DC bus voltage
LV 40V ~ 850V
HV DC bus current
0~100A×8
LV PV input voltage
250~840V
LV PV input current
0~130A×8
Power rating
50kW×8
LV battery dis-/charge mode (Optional)
HV DC bus voltage
LV 40V ~ 850V
HV DC bus current
0~100A×8
LV battery voltage
250~840V
LV battery current
0~130A×8
Power rating
50kW×8
Physical
Cooling
Forced air cooling
Noise
70dB
Enclosure
IP20/NEMA1
Max elevation
3000m/10000feet (> 2000m/6500feet derating)
Operating
ambient
temperature
-20°C to 50°C (De-rating over 45°C
)
Humidity
0~95% (No condensing)
Size (W×H×D)
1100×2060×800mm
Weight
600kg
Installation
Floor standing
Other
Peak efficiency
98%
Protection
OTP, OVP/UVP, EPO, Fan/Relay Failure, OLP
Configurable protection limits
Upper/Lower Voltage, Battery EOD voltage.
Display
Touch Screen
Communication
RS485,CAN,Ethernet
Isolation
Non-isolation
Compliant
CE LVD IEC 62109/62477,
CE EMC IEC 61000
UL1741