4/4
4.5.1- Choose the remote control key's function to program:
- Display the value of the function to program using
and
keys on the RSA Hz PRO.
4.6- Clearing remote controls: Parameter
(factory setting =
)
- Clearing all remote controls is performed by pressing and holding for 3 seconds the key
until dashes
appear.
4.7- Configuration of auxiliary accessories: Parameter
(valeur usine =
)
- The auxiliary contact is a dry contact. A single accessory can be connected and power supplied according to the use configured.
4.8- Configuring the operating time: Parameters
-
)
-
: Motor operating time (factory setting =
= 160 seconds)
>
(increments of 2 sec.) Adjust a time slightly longer than the actual operating time (opening time + 4s.).
-
: Time for reclosing the door (valeur usine =
)
>
(increments of 1 sec.) Enabled in automatic operating mode (§ 4.1).
-
: Delay time before motor reversion (factory setting =
)
Check that the value of the parameter
is equal to
>
(increments of 1 sec.) Particular case of motors not accepting reversion of the rotation direction without stopping phase.
-
: Area lighting time after cycle end (factory setting =
)
>
(increments of 1 minute.)
To return to the menu, press the
and
keys to return to value
(or any other value indicating the product’s operation: see §5) or after a one-minute
waiting time.
4.5.2- Save the channel
(RSA Hz PRO can save maximum 32 channels):
- Press simultaneously the remote control key to program and the key
on the RSA Hz PRO for
three seconds until dashes
appear
- The RSA Hz PRO can be controlled in the three-button mode using a reverter with three keys wired onto the START,SEC2, and SEC3 inputs (if the latter are confi-
gured “non wired”: chapter 4.2).
3s.
3s.
Contact to drive an electric latch
(The latch must be supplied with an outside power supply)
Contact to drive an Orange flashlight without notice
(only during the door's operation)
Contact to drive a zone lighting
(default mode, automatic switch off after timeout T3 - §4.8)
Contact to drive an Orange flashlight with notice
(before starting and during the door's operation)
Contact to drive an electromagnetic latch
Contact to drive an open door indicator
Contact of the stable mono relay type to drive an automation system
Contact of the unstable relay type to drive an automation system
Waiting for a command
Delay before closing door
Opening cell hidden
Closing door in progress
Opening door in progress
Closing cell hidden
ADMAP* cell hidden
Emergency stop triggered
Permanent contact on “START" input
Safety Self-testing
Door movement forced by keypad
Delay before motor reversion
Self-test failed on safety input 2
Self-test failed on safety input 3
Intensity exceeded on 24V power supply
(too many accessories connected)
Operating time “T0” too short
or motor endstop not reached
Safety fault at opening
(contact always open)
Safety fault at closing
(contact always open)
ADMAP* safety fault
(contact always open)
Self-test failed on safety input 1
Operating information
5
List of operating information displayed by RSA Hz PRO used to view and an easy diagnostic of the facility’s status.
Event codes:
Default codes:
Log of the last 10 faults:
: See fault code above.
Cycles counter:
Tens and units,
Thousands and hundreds,
Hundred and tens of thousands, (example :
U2
U1
U0
= 5249 cycles).
Accessories consumption:
:
Puissance consommée en watts de
à
Reset of the RSA Hz after a fault:
To clear the fault codes, select the parameter
then press and hold the
key for 3 seconds until dashes
appear.
- For the fault codes from
to
:
Once the fault is corrected, it is not required to clear the fault code of the log to return to normal operation.
- For the fault codes from
to
:
Once the fault is corrected, you must clear the defect code for the log to return to normal operation.
*If the connection of accessories matches the diagram in chapter 1.
**Area Dangerous for Movement Accessible to the Public.