4.4 

– Inverter / Charger Settings 

The program settings for the PHI 3.8 Batteries with Victron Inverter / Charger products are outlined below. 

Table 3.0 - Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Victron Inverter / Charger 

Program Settings for SimpliPhi Model 3.8 - 48V with Victron Inverters / Chargers 

Phoenix VE.Direct Inverters 

10k Cycles 

(80% DoD) 

5k Cycles 

(90% DoD) 

3.5k Cycles 

(100% DoD) 

Victron Connect 

Static Low Voltage Cutoff 

Output Voltage 

230V 

Output Frequency 

50Hz 

Dynamic Cutoff 

OFF 

Low Battery Shutdown 

50.2 

49.6V 

48V 

Low Battery Restart & Alarm 

54V 

Charge Detect 

54V 

ECO Mode Wake-up Minimum Power 

15W 

ECO Mode Search Interval 

2.5S 

Victron Connect 

Dynamic Low Voltage Cutoff 

Enable Dynamic Cutoff 

ON 

Battery Type 

Custom 

Battery Capacity

1

 

37.5A per PHI3.8; (75A for 2, 225A for 3) 

Voltage for Discharge 0A 

50.2 

49.6V 

48V 

Voltage for Discharge 8A 

50.2 

49.6V 

48V 

Voltage for Discharge 23A 

50.2 

49.6V 

48V 

Voltage for Discharge 66A

2

 

50 

49.1V 

47.5V 

MultiPlus & Quattro  

Inverter Chargers 

10k Cycles 

(80% DoD) 

5k Cycles 

(90% DoD) 

3.5k Cycles 

(100% DoD) 

 VE Configure 

General Tab 

SoC when Bulk Finished 

95% 

Total Battery Capacity

1

 

75Ah per PHI3.8; (150Ah for 2, 225Ah for 3) 

Charge Efficiency 

95% 

 VE Configure 

Inverter Tab 

DC Input Low Shut-Down 

50.2 

49.6V 

48V 

DC Input Low Restart 

50.5V 

DC Input Low Pre-Alarm 

51V 

 VE Configure 

Charger Tab 

Battery Type 

Lithium 

Lithium > Yes 

Lithium Iron Phosphate 

Absorb Voltage 

54.4V 

54.4V 

56V 

Float Voltage 

54V 

Charge Current (C/2)

1

 

37.5A per PHI3.8; (75A for 2, 225A for 3) 

Repeated Absorb Time 

1 Hour 

Repeated Absorb Interval 

7 Days 

Absorb Time 

1 Hour 

 

Notes: 

 

1. Per PHI 3.8 Battery 

– These settings are calculated by multiplying the nominal per battery value times the # of 

batteries. 

 

2. These levels exceed the warrantied recommended operating conditions. 

 

Levels are typical @ 25°C and may need adjusting at temperature extremes. 

 

When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes in 
between. 

 

Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model. 

 

Summary of Contents for PHI 3.8

Page 1: ...r PHI Battery Optimized Energy Storage Management for Residential Commercial Applications Utilizing Efficient Safe Non Toxic Energy Dense Lithium Ferrous Phosphate LFP Chemistry SIMPLIPHI POWER INC RE...

Page 2: ...pliPhi storage technology eliminates operating temperature constraints toxic coolants and the risk of thermal runaway and fire Safe lithium ferrous phosphate No cobalt No hazards SimpliPhi s battery t...

Page 3: ...oller Power Sizing 5 3 0 Victron BMV 700 Installation Setup 5 3 1 Standard Features 6 3 2 Installation Connections 6 3 3 Installation Quick Start Guide 7 3 4 Victron Available Interfaces 8 4 0 Program...

Page 4: ...Based on tests and evaluations the following parameters refer to tables below have been established More information on Victron products can be found on their website https www victronenergy com More...

Page 5: ...controller max 80A B PV 80A 37 5A 2 13 A properly sized PHI Battery bank based on available PV charge would have a minimum of 3 PHI Batteries This maximizes the use of available PV while ensuring the...

Page 6: ...atteries on Apple or Android smartphones tablets Macbooks and other devices 3 2 Installation Connections Follow the instructions below to setup the BMV 700 CAUTION Connect the Negative Pole of the PHI...

Page 7: ...each digit is selected iii Calculate total bank capacity based on number of PHI Batteries in the bank iv Example 75Ah x 3 Batteries 225Ah b Press setup for 2 seconds to enter other parameters of the B...

Page 8: ...quired contact Victron Energy at sales victronenergy com or call Victron at 31 0 36 5359700 4 0 Program Settings for PHI Batteries In order to maintain the Warranty it is critical to ensure that the a...

Page 9: ...may need adjusting at temperature extremes When performing rapid deep charge discharge cycles the PHI Battery should be allowed to rest 15 minutes in between Always refer to the SimpliPhi Power Manua...

Page 10: ...6V 48V Voltage for Discharge 23A 50 2 49 6V 48V Voltage for Discharge 66A2 50 49 1V 47 5V MultiPlus Quattro Inverter Chargers 10k Cycles 80 DoD 5k Cycles 90 DoD 3 5k Cycles 100 DoD VE Configure Gener...

Page 11: ...Current C 2 1 37 5A per PHI3 8 75A for 2 112 5A for 3 Default Charge Settings OFF Absorb Voltage 54 4V 54 4V 56V Absorb Time 1 Hour Float Voltage 54V Equalization Voltage 54V Auto Equalization OFF Tem...

Page 12: ...50 1 49 5V 48V 2C2 49 7 49 1V 48V Restart Offset 1 2V Victron Default Absorption Voltage 54 4V FOR BACKUP ONLY SYSTEM Color Control GX Venus GX Settings Keep Batteries Charged Mode Optimized with Batt...

Page 13: ...For your reference See PHI 3 8 kWh 48V Specifications sheet See PHI 3 8 kWh 48V 10 Year Warranty Failure to adhere to installation protocol will void Warranty 6 0 SimpliPhi Technical Support For techn...

Reviews: