3
579-1034
Setting the address
DIP switch
Each addressable TrueAlert ES notification appliance has a unique address that is set using an eight position DIP switch (ADDR1).
Assign up to 63 unique addresses to an SLC, however, the total appliance loading available may be less due to appliance current
requirements.
To set the address, complete the following steps:
1. Insert a number 1 or number 2 Phillips screwdriver, or a similar sized object, into the opening at the bottom of the appliance and
unclip the appliance from the backplate. See
.
2. Set the switches using a non-metallic stylus, or the equivalent.
3. Record the set address.
Figure 3. Setting the DIP switch address
Setting the horn configuration switch
Figure 4. Setting the appliance configuration
Certain options for the horn can be configured directly on the appliance
using the Configuration switch (CFIG1) on the back of the appliance. See
.
AO Settings
Position 1
Configuration Control: OFF to enable Local
Audible control (positions 2-7 below), ON for
Panel control.
Position 2
Audible Volume: High (OFF), Low (ON).
Position 3
CAN Horn mode: switch must be set to OFF.
Position 4
Legacy NAC mode: switch must be set to OFF.
Position 5, 6, 7,8
These switches are unused by the horn. Leave
them set to OFF.
To access the switches:
ADDR1
The DIP switch shown is
set at address 7
DIP switches 5 and 6
DIP
switches
1 through 4
Not used
Reserved for
future use
To access the switches:
Device
configuration switch
CFIG1
Not used (Leave at OFF)