Simplex TrueAlert ES Series Installation Instructions Download Page 2

2

579-1034 

Wiring instructions

1. At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the backplate. 
2. To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds. 
3. Ensure that correct polarity is maintained for each unit.
4. Signaling Line Circuit (SLC) wiring must be twisted pair (TWP). CKT terminals accept two wires: 12-18 American Wire Gauge (AWG) 

TWP . 

Wiring notes  

WARNING:

Make sure that all power is disconnected before starting the installation.

IMPORTANT:

 

Do not bring the conduit through the rear of the electrical box. Strip the lead insulation to 7/16 inch 

maximum.

Figure 2. Wiring instructions

The maximum number of appliances on a circuit is 63. The maximum wire resistance between appliances is 26 ohms. See the field wiring diagrams 
for the driving compatible fire alarm control panel for further instructions.

Notification appliances are rated using an individual module label.

Maintain the correct polarity on the terminal connections. 

Terminals 1 and 2 can each accommodate two wires, one wire going in and one wire going out to the next appliance. 

TrueAlert SLC wiring connections are supervised and power-limited.

These appliances are rated to the operating voltage limits of 17-31 VDC. The appliance may fail to operate as intended, and cause permanent 
damage to this equipment if it operates outside of these limits.

Only operate the TrueAlert ES AO appliances using a compatible power supply.

T-tapping is not permitted on Class A wiring.

!

Appliance backplate

From a compatible
SLC controller,
see notes

Terminal 2
CKT+ 

Terminal 1
CKT- 

(T-tapping example)

    A/O

    A/O

    A/O

    A/O

    A/O

    A/O

    A/O

From a compatible
SLC controller,
see notes

Class A wiring, see notes

Class B wiring, see notes

To the next appliance
or compatible SLC
controller, see notes

Summary of Contents for TrueAlert ES Series

Page 1: ... the mounting surface See Figure 1 for mounting and location information 2 Bring the building wiring through the rectangular opening in the backplate 3 Connect the building wires to the backplate See the wiring section on page 2 4 Secure the backplate to the electrical box using the provided hardware Install with the writing Install this side up at the top Use a torque wrench to tighten the screws...

Page 2: ...agrams for the driving compatible fire alarm control panel for further instructions Notification appliances are rated using an individual module label Maintain the correct polarity on the terminal connections Terminals 1 and 2 can each accommodate two wires one wire going in and one wire going out to the next appliance TrueAlert SLC wiring connections are supervised and power limited These applian...

Page 3: ... Setting the DIP switch address Setting the horn configuration switch Figure 4 Setting the appliance configuration Certain options for the horn can be configured directly on the appliance using the Configuration switch CFIG1 on the back of the appliance See Figure 4 AO Settings Position 1 Configuration Control OFF to enable Local Audible control positions 2 7 below ON for Panel control Position 2 ...

Page 4: ...92 4 31 Max 94 4 93 9 Low volume setting 17 Min 84 1 83 6 23 86 7 86 6 31 Max 89 1 88 6 Notes 1 The coded category covers both Temporal and March time cadences 2 Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL s reverberant test chamber 3 High and low volume settings are configured with DIP switch CFIG1 on the controller 4 If you install the ...

Reviews: