3
S4906-0005-3 5/2013
110
75
30
15
FACP
Optional 4905-9915 (white) or 4905-9916 (red)
Adapter, recommended for surface mounted box
Wiring terminals and address setting
are located behind the housing
Ceiling reference,
surface mounted box
Ceiling reference,
flush mounted box
Strobe intensity viewing slot
Intensity selection plug,
accessible only from rear of
lens housing; factory setting is
FACP, controlled by panel
Optional 4905-9928
Adapter Plate, required
for surface mounted
electrical box
Optional 4905-9927
Red Wire Guard
Four mounting clamps
included, two each side
End View
Magnetic test area
LED indicator
Strobe housing straight-on view
4" (102 mm)
square box,
1-1/2" (38 mm)
minimum depth
Compatible Controller
Data Sheet
Reference
Controller
Output
IDNAC SLC
Output Voltage
Appliance Voltage
Design Reference
4100ES with EPS+ or EPS Power Supply
S4100-0100
IDNAC SLC
29 VRMS
(regulated)
23 VRMS
(with 6 VRMS drop)
4009 IDNAC Repeater
S4009-0004
General Specifications
(see page 2 for dimensions)
Environmental
32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections
Terminal blocks for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm
2
); two wires per
terminal for in/out wiring
Reference
Installation Instructions 579-808
Electrical Specifications
Typical Operating Voltage Range
23 VRMS to 31 VRMS, Special Application (see page 4 for 17 VRMS rating)
Flash Rate and Synchronized SLC Loading
1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30
Ω
resistance between appliances
Candela
Setting
15 cd
30 cd
75 cd
110 cd
Horn Output Selection
High Low High Low High Low High Low
23 VRMS
Current Ratings, for connection to
IDNAC Addressable SLCs, horn steady on
75 mA
70 m A 110 mA
105 mA
198 mA 193 mA 250 mA
245 mA
Horn Output Characteristics
2400 to 3700 Hz sweep, modulated at 120 Hz rate
Horn Output Ratings
@ 10 ft (3 m)
Sound Type (see Note)
Steady
Coded
Setting
High Low High Low
Reverberant Chamber,
UL 464 Test
84.6 dBA
79.1 dBA
80.6 dBA
75.5 dBA
Anechoic Chamber
90 dBA
84 dBA
86 dBA
80 dBA
Note:
Coded horn values are typical of the output measured with a Temporal or March Time pattern and with a sound level meter
reading on a “fast” setting. Under the same test conditions, coded horn output “peak” sound level readings are typically 4 dBA