The specifications below apply to both analog and digital amplifiers.
Supply
voltage:
19.7-31.1
VDC
Output
voltage:
25
VRMS
or
70.7
VRMS
Maximum output power:
Flex-35 = 35 W; Flex-50 = 50 W
Flex-50
Alarm state:
5.55 A (signal)
74 mA (card)
Supervision state:
351 mA (signal)
74 mA (card)
Low power state
(NACs in supervision, no power to power stage):
0
A
(signal)
85
mA
(card)
Flex-35
Alarm state:
4.00 A (signal)
74 mA (card)
Supervision state:
351 mA (signal)
74 mA (card)
Low power state
(NACs in supervision, no power to power stage):
0
A
(signal)
85
mA
(card)
The equipment operates normally with ambient temperatures outside the cabinet from 32
°
to
120
°
F (0
°
to 49
°
C), inclusive.
The equipment operates normally under non-condensing humidity conditions up to 93% relative
humidity at 90
°
F (32
°
C).
Amplifier Specifications