If you are experiencing poor or no audio from the fiber optic audio repeater,
refer to Table 6 below.

Table 6.  Troubleshooting

Check

Comments

Does the master/slave module have the correct
voltage input?

The voltage input should be between
24 and 28.8 VDC.

Is the power LED ON?

Check input for voltage.

Are both carrier LEDs ON?

ON = a good fiber signal

Is the correct signal level present at the master
input?

The level should be 1V P-P Audio.

Is the correct signal level present at the slave
output?

The level should be 1V P-P Audio.

Are the correct connectors being used?

ST Connectors

Is the optical connector on the master/slave clear
of any obstruction or dirt?

Are the ends of the fiber connectors free of all dust
or dirt?

Is the fiber broken in the connector?

Is the fiber protruding from the tip of the connector?

Use Fiber Optic Inspection Scope (FT890A)

Is the fiber connection properly seated?

Visually check as required.

Is the fiber optic cable pulled to sharply around a
corner?

A minimum two-inch bend radius on the fiber
optic cables must be maintained.  A bend radius
less than two inches may permanently damage
the optical fibers.

Is the correct size fiber cable being used?

62.5/125 multi-mode graded index is preferred.
However, 50/125 cable is also acceptable.  See
the “Specifications” section of this publication for
distance limitations.

Does the fiber cable pass light in any amount?

Use a flashlight or similar source to conduct the
test.

Does the fiber run have too much attenuation for
the system?

There should be a maximum of loss of 10db.
Fiber Tester - TS055A   Optical Source - TS056A

Note:

If problems still exist, set the system up locally by using a small fiber patch cord (EFN062-002M) with short copper
lengths.  This test may be setup with or without the fiber units.

Do not attempt to repair the unit.  In case of trouble, please contact your local
Simplex Time Recorder Company branch office for repairs.

Consult your local telephone directory for the phone number listing of the
Simplex branch office, or call the Simplex Customer Assistance Department at
(978) 632-2500, and request the telephone number for the Simplex branch office
in your area.

Troubleshooting

Troubleshooting Table

Repair

firealarmresources.com

Summary of Contents for 4190-9011

Page 1: ...600 ohm audio signal The audio repeater uses either 62 5 125 or 50 125 fiber optic cables for distance limitations reference Table 4 The Fiber Optic Audio Repeater can be utilized in one way drop and...

Page 2: ...interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules which are designed to provide r...

Page 3: ...ons Specifications Terminal Voltage Terminal 1 24 VDC Terminal 2 0 V Table 1 Power Connections Table 2 Audio Connector Pin Out Terminal Connection Terminal 1 Audio OUT Terminal 2 Audio OUT Terminal 3...

Page 4: ...iber 10 000 ft 3 km Maximum Distance pt pt 50 125 Fiber 6 500 ft 2 km Operating Temperature 40 F to 158 F 40 C to 49 C Storage Temperature 40 F to 185 F 40 C to 85 C Power Requirement 24 to 28 8 VDC 1...

Page 5: ...NOT USED CHNL B CHNL A SUPERVISION CONTACTS CLOSED OK 4190 9012 SLAVE FIBER OPTIC AUDIO MODEM P N 618 020 INSTALLATION INSTRUCTIONS 574 795 REV _ Channel B Relay Channel A Relay Ground Audio Out Audi...

Page 6: ...t on the audio repeater IMPORTANT To ensure a proper ground connection tighten the screws sufficiently for the star washers to cut the plating on the audio repeater 3 Install the bracket audio repeate...

Page 7: ...t be interfaced at the 1 V p p level The destination of the low level audio may be one of three possible locations The input to a 25 W amplifier The input to a 100 W amplifier The network input to an...

Page 8: ...the audio repeater fiber connections these contacts are typically connected in series with the EOL resistor in a local monitor circuit such as a zone or ZAM If separate annunciation is desired two mon...

Page 9: ...95 for suitable power supplies 6 Neatly dress all cables that are cut and stripped CARRIER ON OK 4 3 2 SUPERVISION CONTACTS CLOSED OK CHNL B CHNL A AUDIO OUT 2V P P MAX 4190 9012 SLAVE FIBER OPTIC AUD...

Page 10: ...d radius on the fiber optic cables must be maintained A bend radius less than two inches may permanently damage the optical fibers Is the correct size fiber cable being used 62 5 125 multi mode graded...

Reviews: