background image

Figure 6: Installing the Motherboard in a 4100ES Expansion Bay

4.

If you are installing the leftmost motherboard, connect a 733-525 Power and Communication Harness. Continue to the next topic to connect the

harness.

Connecting the 733-525 Harness

If you need to connect a 733-525 Harness to a motherboard, refer to Figure 7 and follow these steps. Make sure to route the power and

communication wiring on the left side of the bay.

1.  Connect one end of the harness to a motherboard in an adjacent bay. If the adjacent bay is the CPU bay, connect the harness to the P8 and

P7 connectors of the CPU motherboard.

-  Insert the harness connector with the blue wire into the P8 connector. Note that the P8 connector has eight pins. Insert the harness

connector on either the top four pins or the bottom four pins, not in the middle.

-  Insert the harness connector with the white wire into the P7 connector. Note that the P7 connector has eight pins. Insert the harness

connector on either the top four pins or the bottom four pins, not in the middle.

-  If the adjacent bay is an expansion bay, connect the harness to the P2 and P3 connectors of the motherboard installed in the leftmost slot.

(If an SDACT or CCDACT occupies the leftmost slot, connect the harness to the motherboard in the second slot from the left.) Connect the

harness as follows:

-  Insert the harness connector with the white wire into the P3 connector. Note that the P3 connector has eight pins. Insert the harness

connector on either the top four pins or the bottom four pins, not in the middle.

page 7

579-221  Rev. F

4100-6038 Dual RS-232 Module Installation Instructions

Summary of Contents for 4100-6038

Page 1: ...ested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when...

Page 2: ...igned to each jumper pin The specific jumper settings required on the dual RS 232 card depend on the type of device being attached to the card Refer to Table 1 for specific jumper configurations Figur...

Page 3: ...1 2 1 2 AC Printer 3rd Party Computer Supervised 2 3 2 3 1 2 1 2 1 2 1 2 None 2 3 2 3 2 3 AC Printer Unsupervised 2 3 2 3 1 2 1 2 1 2 1 2 1 2 2 3 2 3 1 2 Setting Switches Switches Switch SW1 on the R...

Page 4: ...Figure 3 4100 Daughter Card Addresses page 4 579 221 Rev F 4100 6038 Dual RS 232 Module Installation Instructions...

Page 5: ...When installing 2 51 mm x 11 inch 292 mm motherboards in a 4100ES expansion bay adhere to the following guidelines Each expansion bay assembly includes a chassis two end supports one LED switch frame...

Page 6: ...nd fill to the right 1 Orient the motherboard with the connector labeled J1 on the right and the header labeled P1 on the left 2 Attach four metal threaded standoffs and lockwashers into the screw hol...

Page 7: ...eight pins Insert the harness connector on either the top four pins or the bottom four pins not in the middle Insert the harness connector with the white wire into the P7 connector Note that the P7 co...

Page 8: ...bay Insert the harness connector with the blue wire into the P2 connector Note that the P2 connector has eight pins Insert the harness connector on either the top four pins or the bottom four pins no...

Page 9: ...tinuity of the shield must be maintained throughout the entire cable length The entire length of the cable must have a resistance greater than 1 Megohm to earth ground Underground wiring must be free...

Page 10: ...be kept to a minimum inside the back box enclosure The wiring should be neatly dressed and bundled together using the wire ties provided with the equipment Anchor power limited wiring to tie points as...

Page 11: ...G 2 081 mm 2 or 625 feet 191 meters for 12 AWG 3 309 mm 2 All wiring is 18 AWG 0 8321 mm 2 or to local code Use of CTS line is required with or without supervised circuit When using Service Modem 565...

Page 12: ...tional listings may be applicable contact your local Autocall product supplier for the latest status Listings and approvals under Tyco Fire Security GmbH and the product names listed in this material...