background image

To check the status

To activate

To test

To reset

Simplex Outdoor Isolated Callpoint

120.515.787_SPX-D-MCP830-DS. doc. version 1.0. 9. April 2018.

©2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of 
document revision date and are subject to change without notice. 
www.simplex-fire.com

Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland

 

Operation

To remove the unit from the backbox

 

Maintenance

Specifications

Approvals

All required Declarations and certificates are publicly available on the websit

www.simplex-fire.com

 and are searchable by number or model name.

The above fire detection products are components designed for use in Addressable Systems exclusively available to registered partners only. They are intended for installation 
by trained registered personnel only. Systems should be installed and configured according to local regulations.

The “Status LED” is shown on the previous page, its conditions are: ”not 
activated” – this is normal; “activated yellow” – there is a short circuit on 
the loop. This must be rectified as quickly as possible; “activated red” – the 
callpoint has been activated, indicating that there is a fire alarm state within 
the building.

To activate the callpoint press on the position marked (large dot). This 
allows a spring to push the plastic element downwards, so closing a switch 
and triggering a signal to the control panel.

A test/reset key is provided to activate the callpoint for testing. Insert this 
into the slot in the bottom of the unit and pull the sliding plate (lower half 
of the front face) downwards. (Note this potentially causes an alarm). 
Remove the key.

The deformable element also allows you to test by activating the callpoint 
as normal. This is non-destructive.

To reset the callpoint, follow the ‘To test’ procedure above –pulling the 
sliding plate downwards allows the element to snap back to its non-
deformed state.

To replace the glass or deformable element

Follow the ‘To test’ procedure above. Pull down further on the sliding plate 
until it is free of the unit. Remove the deformable element, pulling away 
the bottom first. Fit the replacement then push the sliding plate upwards 
until it snaps back into place.

1

Remove the back box locking screws.

2

Gently lever the callpoint away from the back box by twisting a flat 
bladed screwdriver in the slots between them.

Parameter

Value

Parameter

Value

System Compatibility

Use only with the Simplex SX501 Fire 

Alarm Controller

Operating Humidity

Up to 95 %

.

non-condensing

Environment

Outdoor applications 

Dimensions (HWD)

93 x 97.5 x 73 mm 

Operating Temperature

-25 to +70 

o

C

Weight

240 g

Storage Temperature

-30 to +70 

o

C

IP Rating

IP67

Material

Flame Retardant ABS, glass reinforced

CPR

CPR Approval

European Type Approvals

Declaration of Performance

EN54-11

EN54-17

LPCB

DoP-2015-4170