page 2
579-1317 Rev 1
Sounder and Sounder Beacon Installation Instructions
Product
Details
4905-5205
Flush Backbox Adaptor for Indoor Wall Sounder
4905-5206
Deep Surface Back Box for Indoor Wall Sounder Red
4905-5207
Deep Surface Back Box for Indoor Wall Sounder White
General Information
4098-5217
4098-5220
4906-5210
4906-5211
4906-5212
4906-5213
4906-5214
4906-5215
Mounting
orientation
Ceiling
Wall
Indoor/
Outdoor
Indoor
Outdoor
Indoor
Outdoor
Weight (g)
146 g (5.15 oz) 154 g (5.4 oz)
182 g (6.4 oz)
182 g (6.2 oz)
358 g (12.6 oz) 194 g (6.8 oz)
194 g (6.8 oz)
372 g (13.1 oz)
Operating
temperature
(°C)
0°C to 70°C (-32°F to +158°F)
0°C to 49°C (32°F to 120°F)
-25°C to +70°C
(-13°F to
+158°F)
0°C to 49°C (-32°F to 120°F)
-25°C to +70°C
(-13°F to
+158°F)
Storage
temperature
(°C)
-25°C to +70°C (-13°F to +158°F)
Humidity
Up to 95% non-condensing
Sounder
volume
settings
4
2
Isolator
Yes
Beacon flash
rates
-
0.5 Hz and 1 Hz -
-
-
0.5 Hz and 1 Hz
Typical Sounder output at 1 metre (3.28 feet)
High volume
90 dBA
100dBA
Mid High
volume
80 dBA
-
Mid Low
volume
70 dBA
-
Low volume
60 dBA
90 dBA
Loop loading (with 4098-525X series addressable detector fitted to the base variants)
Sounder volume
Beacon flash rate (if
applicable)
Wall sounder
Wall sounder beacon Base sounder
Base sounder beacon
OFF
OFF
0.35 mA
0.35 mA
0.88 mA
0.88 mA
LOW
OFF
3.2 mA
3.2 mA
3.0 mA
3.0 mA
HIGH
OFF
8.6 mA
8.6 mA
4.8 mA
4.8 mA
HIGH
0.5 Hz
-
11.2 mA
-
8.0 mA
HIGH
1 Hz
-
13.6 mA
-
9.6 mA
Note:
Please refer to the loop loading calculator for these units.
Address programming and configuration
Default address = 255. Set the address before installation using either the 850EMT or 801AP service tool with its ancillary lead. Remove the front cover
to access the programming port on wall devices. The 850EMT tool can be used to set the tone, flash rate and volume level. Refer to the document
125.515.058: 850 Engineering Tool User Manual for details.