background image

General wiring guidelines

•  Conductors must test free of all grounds.
•  All wiring must be done using copper conductors only, unless

noted otherwise.

•  The required wiring is unshielded Twisted Pair. This wiring must

have a capacitive rating of less than 60pf/ft and minimum 3 twists

(turns) per foot.

•  • If shielded wire is used:

-  The metallic continuity of the shield must be maintained

throughout the entire cable length.

-  The entire length of the cable must have a resistance greater

than 1 megohm to earthground

•  In areas of high lightning activity, or in areas that have large power

surges, the 2081-9027 Transient Suppressor should be used on

monitor points.

•  Wires must not be run through elevator shafts.
•  Splicing is permitted. All spliced connections must either be

soldered (resin-core solder), crimped in metal sleeves, or

encapsulated with an epoxy resin. When soldering or crimped

metal sleeves are used, the junction must be insulated with a high-

grade electrical tape that is as sound as the original insulating

jacket. If shielded wiring is used, shield continuity must be

maintained throughout.

•  A system ground must be provided for earth detection and

lightning protection devices. This connection must comply with

approved earth detection per NFPA780.

•  Only system wiring can be run together in the same conduit.
•  Underground wiring must be free of all water.

Note:

Although the required wire for IDNAC circuits is twisted pair (controlled impedance) wiring, some applications will wish to take advantage of existing

wiring that is not twisted pair. This is only allowed if both conductors of the IDNAC circuit reside in the same metal conduit, and only under certain

conditions. Check with your local sales office before using wiring that is not twisted pair.

Device wiring guidelines

Review the following guidelines for devices before you begin the field wiring.

•  Only IDNAC devices and other compatible devices are allowed on

the SLCs. Consult the Extended Power Supply manual, 579-1015,

for a list of compatible devices.

•  Maximum of six isolators between any appliance and SLC

terminals. Maximum 12 isolators per SLC.

•  Maximum 30 devices connected directly to any isolator terminal

pair.

•  All wiring is 20 AWG to 12 AWG.
•  All wiring is supervised and power-limited.

•  The maximum alarm current is 3 A.

Note: In a Class A extension wiring configuration, the maximum

loop current is limited to 3A max. In this configuration, the

repeater extends the wiring distance but does not increase the

current available for the devices.

•  Maximum cable load is 10,000 feet (3,048 m) per channel.

Maximum wire length from the Class A Adapter to any device is

4,000 feet (762 m).

•  The nominal voltage rating is 29 VDC.
•  Follow the IDNAC Speaker Wiring Application Guidelines in

579-1015 EPS Installation Instructions for TrueAlert ES speaker

and S/V appliances.

Ferrite Beads

A ferrite bead must be installed on the IDNAC input wiring, and the IDNAC output wiring. To install the ferrite bead:

Figure 5: Ferrite bead installation

1.

Loop the wire though the ferrite bead close to the Repeater field wiring terminals for lowest radiated emissions (before the wires leave the box).

Do not loop the ground wire on the AC wiring through the ferrite bead.

2.

Secure the ferrite bead with the provided cable ties.

page 4

579-1080  Rev. F

4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide

Summary of Contents for 4009-9814

Page 1: ...r more information on the 4009 IDNAC Repeater referred to as Repeater from this point on in the manual Card specifications Table 1 Card specifications Card Specifications Operating Conditions 32 o F 120 o F 0 o C 49 o C Up to 93 relative humidity at 90 o F 32 o C non condensing Electrical Specifications IDNAC Output 29V Special application 3A Max IDNAC Input for Class A Extension mode 4 unit loads...

Page 2: ...d J2 on the Repeater and jumper J1 on the Class A Adapter card must be set to the same setting For a local Class A loop To create a Class A local loop off of the repeater set the jumper to the Local setting jumper position 1 2 For an extended Class A loop To make the repeater part of a Class A loop extending from a DCAI set the jumper to the Class A Ext setting jumper position 2 3 Figure 3 Class A...

Page 3: ...installed on the repeater the TB1 on the Class A Adapter replaces the TB1 IDNAC OUT on the repeater It s important that nothing be connected to the repeater s TB1 Figure 4 Use the Class A Adapter terminal block page 3 579 1080 Rev F 4009 9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide ...

Page 4: ...rs of the IDNAC circuit reside in the same metal conduit and only under certain conditions Check with your local sales office before using wiring that is not twisted pair Device wiring guidelines Review the following guidelines for devices before you begin the field wiring Only IDNAC devices and other compatible devices are allowed on the SLCs Consult the Extended Power Supply manual 579 1015 for ...

Page 5: ...Class A Loop Mode Configuration Note To achieve this a 4100 6103 Dual Class A Isolator DCAI must be part of the EPS configuration manual 579 1029 The Extended Class A Loop Mode does not support the 4905 9929 TrueAlert Isolator Module To wire the Repeater as part of an Extended Class A loop 1 Route the wire coming from the DCAI to the A and the A inputs on the Class A Adapter terminal block that is...

Page 6: ...Figure 7 Extended Class A loop wiring page 6 579 1080 Rev F 4009 9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide ...

Page 7: ...card 1 Open or create a job in the ES Programmer 2 Open the Hardware Tab 3 Double click on the Icon of the EPS module that the Class A Adapter s 4009 IDNAC Repeater is installed on to open the Properties window 4 Open the Point Editing tab 5 Select the Repeater in the Select Device drop down menu 6 Go to the Repeater Operation drop down menu and select the setting that represents the jumper config...

Page 8: ...nal listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co Simplex and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA ...

Reviews: