background image

3

Expansion Power Supply (EPS) Installation Instructions

Panel interconnections

Use the following steps and the figure on the next page to 
connect the EPS to the Main System Board (MSB).

1.

Remove AC and battery power from the panel. 

You 

will be wiring to the AC line. 

Be sure the circuit 

breaker is OFF and tagged.

2.

You have the option of removing the Depleted Battery 
Cutout jumper (

R76

) on the EPS. Removing the 

jumper has the following effects:

-

The system will NOT initiate an alarm if the first 
alarm occurs after the depleted battery state has 
been detected.

-

The system will shut down 60 seconds after the 
depleted battery condition is detected.

Remove the jumper if required. Note that there is a 
corresponding option in the programmer that must be 
set; see the 

Front Panel Installing, Operating, and 

Programming Instructions

 (579-704 for 4006, 

579-716 for 4008).

3.

Connect the data flex harness (166-438) from 

J1

 on 

the EPS to

-

J8

 on the 4006-9801

-

J3

 on the 4008-9801

4.

The AC harness (734-179) is used to connect AC 
power from the MSB to the EPS.

-

AC source is 120 VAC, 60 Hz (single phase) 

or

 

240 VAC (nominal), 50 Hz (single phase).

-

Strip 3/8" insulation from the black and white 
wires.

-

Connect the black wire lead to the LEFT MSB 
AC power terminal (

TB4

) marked “LINE.”

-

Connect the white wire lead to the RIGHT MSB 
AC power terminal (

TB4

) marked “NEUTRAL.”

-

Connect the snap-on AC harness connector to 

P6

 

on the EPS.

5.

Connect the battery harness (734-180) from 

P3

 on the 

EPS to the battery connector on the MSB (

P13

 on the 

4006; 

P14

 on the 4008). Do not connect the harness to 

the batteries until you are ready to power up the 
system. Connectors should be aligned such that:

-

On P13 or P14 on the MSB, the red wire is on the 
left and the black wire is on the right.

-

On P3 on the EPS, the red wire is on the bottom 
and the black wire is on top (closer to R76; see 
the figure on the next page).

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for 4008-9801

Page 1: ...PS assembly bracket with two PCBs Screws washers 441 002 qty 2 AC harness 734 179 black white leads Battery harness 734 180 red black leads Data flex harness 166 438 flat cable Note This document contains instructions on installing the EPS into the fire alarm control panel For programming instructions refer to the Front Panel Installing Operating and Programming Instructions 579 704 for 4006 or 57...

Page 2: ...s Mounting Mount the EPS to the main annunciation cabinet as shown in the figure below Figure 2 Mounting the EPS Fasten the EPS to the cabinet with two slotted torx screws 441 002 EPS MAIN CABINET Screwholes Technical Manuals Online http www tech man com ...

Page 3: ...or 4008 3 Connect the data flex harness 166 438 from J1 on the EPS to J8 on the 4006 9801 J3 on the 4008 9801 4 The AC harness 734 179 is used to connect AC power from the MSB to the EPS AC source is 120 VAC 60 Hz single phase or 240 VAC nominal 50 Hz single phase Strip 3 8 insulation from the black and white wires Connect the black wire lead to the LEFT MSB AC power terminal TB4 marked LINE Conne...

Page 4: ...N TB4 RIGHT ON P6 TINTED AREA PORTION OF BOTTOM BOARD OBSCURED BY TOP OF ASSEMBLY REMOVE POWER FROM AC AND BATTERY TERMINALS AND FROM EXPANSION POWER SUPPLY R76 DEPLETED BATTERY CUTOUT JUMPER CIRCUIT BREAKER BEFORE WIRING THE WHITE RIGHT ON TB4 LEFT ON P6 BLACK RIGHT ON P13 P14 ON P3 TOP ON P3 J3 on 4008 J8 on 4006 DEPLETED BATTERY CUTOUT JUMPER R407 on 4008 R313 on 4006 MAIN SYSTEM BOARD P14 on 4...

Page 5: ...122 F Alarm Current Amps Max Distance from Panel to Last Device Feet Line Resistance Ohms 18 AWG 16 AWG 14 AWG 12 AWG 0 25 840 1335 2126 3382 12 0 50 420 667 1063 1691 6 0 75 280 445 709 1127 4 1 00 210 334 532 845 3 1 25 168 267 425 676 2 4 1 50 140 222 354 564 2 1 75 120 191 304 483 1 71 2 00 105 167 266 423 1 5 CLASS B WIRING CLASS A WIRING TYPICAL AUDIBLE VISIBLE APPLIANCES B B A A B B A A A A...

Page 6: ...610 9111 4606 9101 Annunciators If wiring is routed outside the building use of a listed secondary protector is required Use 2081 9044or 2081 9028 A protector must be installed at each building exit entrance Each 2081 9044 adds 6 Ohms resistance at 200 mA Each 2081 9028 adds 0 2 Ohms wiring resistance and is rated for more than the 0 5 A aux 24 V capacity If the circuit is used to power the Model ...

Page 7: ...e per NAC All other regulated 24 VDC synchronized notification appliances require the use of their associated Listed external synchronization module Notification Circuit rating is 1 5 A maximum 1 35 A maximum strobe load per power supply Table 1 NAC Ratings 15Cd 30Cd 75Cd 110Cd 4906 Rated Current Max per NAC Rated Current Max per NAC Rated Current Max per NAC Rated Current Max per NAC 9101 0 060 3...

Page 8: ...ges or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate equipment NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is op...

Reviews: