9-17
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Common Ground
Fault LED Control
Select and utilize the LED Yellow point type for custom control ground fault LED trouble
indications:
Program the Color User Interface,
Point Editing
Tab as follows:
Add the following custom control equation to the 4007ES IDNAC Addressable Panel:
[INPUTS]
STATUS ON
1-0-9 | CARDSTAT | CSP | POSTIVE EARTH
OR STATUS ON
1-0-10 | CARDSTAT | CSP | NEGATIVE EARTH
OR STATUS ON
1-0-27 | CARDSTAT | CSP | POSITIVE EARTH ON RUI
OR STATUS ON
1-0-28 | CARDSTAT | CSP | NEGATIVE EARTH ON RUI
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
[END OUTPUTS]
Add the following custom control equation to the 4007ES Hybrid Panel:
[INPUTS]
STATUS ON
1-0-3 | CARDSTAT | CSP | POSITIVE EARTH GROUND
OR STATUS ON
1-0-4 | CARDSTAT | CSP | NEGATIVE EARTH GROUND
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
[END OUTPUTS]
HW Ref.
Switch Mode
Ref. Address
Ref. Label
HW Ref. LED Mode
3-1-1
SMPL
3-2-1
ON
P535
Ground Fault
3-1-2
SMPL
3-2-2
SMPL
3-1-3
SMPL
3-2-3
SMPL
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......