DIP SWITCH SELECTABLE PROGRAMMING
SYSTEM WALK TEST
— Activating an initiating de-
vice will cause the indicating appliance to signal a
simple code (zone number) without actuating the
municipal connection or auxiliary alarm outputs and
will then automatically reset. Momentarily opening a
monitor zone or signal circuit will cause the indicat-
ing appliance to operate for 4 seconds, thereby
testing electrical supervision.
ALARM VERIFICATION
— Activation of any smoke
detector will initiate an alarm verification cycle. The
control will retard the activation of the indicating ap-
pliances for 30 seconds. During this delay, if any
other device activates, the alarm will be confirmed
and the indicating appliances energized. If a second
device does not activate during the 30-second delay,
the control will reset and begin a 60-second confir-
mation cycle. During the confirmation cycle, should
any device alarm, on any zone, the indicating appli-
ance circuit will energize. Should the verification
cycle end without “incident” the panel will return to its
normal state. Manual stations, heat detectors, and
waterflow switches will always cause the fire alarm
control to activate immediately.
TEMPORAL PATTERN
— Causes the indicating ap-
pliances to sound the temporal pattern.
ALARM SILENCE INHIBIT
— Disables the signals
silence and system reset switches for 1 or 3 minutes.
AUTOMATIC SIGNAL SILENCE
— Silences the
alarm signals after 20 minutes.
3
TB1
F1
SW4
F2
F3
F4
TB2
+24
OV
+5
TB3
TP4
BA
T-
BA
T+
XFMR
XFMR
SIGA+
SIGB-
SIGA-
SIGB+
Z1+
Z1-
Z2+
Z2-
Z3+
Z3-
Z4+
Z4-
NO
C
NC
NO
C
NC
NO
C
TP1
TP5
H1
POT1
POT2
TB4
TP3 TP2
TP6
1
2
3
4
5
6
1
10
1 2 3
6 5 4
H2
0V
RPWR
GND
GND
5A
2A
2A
6A
3.3k, 1W, 5%
+
-
2A @ 30 VAC / VDC
10k, 1/2W, 5%
10k, 1/2W, 5%
+
+
+
+
+
-
+
-
L G N
T1
120V 60HZ
1.2A
POWER SUPPLY
TROUBLE
BROWN
OUT
TROUBLE
EARTH
TYPICAL 4001-9304C SYSTEM LAYOUT
TYPICAL WIRING CONNECTIONS. FOR MORE DETAILED WIRING INSTRUCTIONS, REFER TO
OPERATION AND INSTALLATION INSTRUCTIONS, S01575-109.