background image

Life Alarm

Fire Alarm Systems

Fire Alarm Controls

4001-9304C

FEATURES

Four monitor zones

Up to 18 two-wire smoke detectors per zone

Signal circuits — 2 class B or 1 class A —
field configurable

Selectable alarm verification

Self-contained audible trouble signal

One normally open city contact

One form C alarm auxiliary contact

One form C trouble contact

Transient suppression for municipal
connections on power supply

Automatic battery charger

Standby batteries

Surface or semi-flush mounting

Alarm/trouble system walk test

Alarm resound

Battery supervision

Earth ground supervision

Brown out supervision of AC power

Automatic signal silence

DIP switch selectable programming

End-of-line devices and batteries included

ULC Listed to CAN-ULC-S527-99

®

©2003 SimplexGrinnell Canada Ltd.

S01575-110-2 10/03

Simplex

®

ZONE

ALARM TROUBLE

TROUBLE

AC POWER ON

ALIMENTATION

SYSTEM TROUBLE

TROUBLE SYSTEM

SIGNALS SILENCED

ARRET ALARME

ALARME

ZONE

1

2

3

4

FIRE ALARM CONTROL

PANNEAU DE CONTROLE AVERTISSEUR D’INCENDIE

4001-9304C

OPTIONS

Option Board - supervised annunciator output

- auxiliary resettable power
- non-silenceable trouble contact

Semi-flush trim kit

External battery & cabinet for 60 hour backup

SPECIFICATIONS

Input ..................................1.2A @ 120VAC 60 Hz

Humidity .................85% non-condensing @ 30°C

Temperature .......................................0°C to 49°C

Weight...............Approximately 10kg c/w batteries

Colour ..........................................................Beige

Knockouts .......................................................1/2”

ULC Listed

Reviews: