Components — Message Interface (MI-100)
Statement
Various meaningful values are possible, depending on the
source of the statement (subject to SIMON LINK updates):
–
*
: Failure
–
ZI
:
~ Failure
~ Mains failure
~ WTS close on wind / rain
~ Signal 1 / 2 / 3 / 4 / 5 (digital input)
–
SI
/
SI*
:
~ Failure
~ ALARM triggered
~ ALARM on line 1 / 2 / 3
~ Reset signal
–
MR
/
MR*
:
~ Failure
~ Alarm triggered
~ Command Open
~ Command Close
–
MI
:
~ Failure
~ Relay on 1 / 2 / 3 / 4
Logical operation
The relays only differentiate between ON and OFF and in the
same way the logic operations only differentiate between
YES and NO. This means:
NOT ( NOT ( statement)) = statement.
Logical operators are defined as follows:
–
NOT
:
–
AND
:
–
OR
:
Examples
– The statement “ALARM from indicating line 1” on the
SI-100 is to be evaluated:
SI*: Alarm_on_Line_1
– The system is in OK operating state:
NOT( *:Failure)
– The statement “ALARM from indicating line 2” of the first
SI-100 and not on the second SI-100 is to be evaluated:
SI1: Alarm_on_Line_2
AND
NOT SI2: Alarm_on_Line_2
– The statement “ALARM from indicating line 1” of the first
SI-100 and not from the other two indicating lines:
SI1: Alarm_on_Line_1
AND
NOT (SI1: Alarm_on_Line_2 OR
SI1: Alarm_on_Line_3)
2.7.2.b Switching delay
After reaching the condition (logical statement is
true), the dry contact (relay) is switched either as
long as the condition remains true or for a preset
time (1 second to 1 hour)
2.7.2.c Hold time
After reaching the condition (logical statement is
true), the dry contact (relay) is switched either as
long as the condition remains true or for a preset
time (1 second to 1 hour).
Even if the condition changes during the hold time, the relay
remains switched until the hold time has elapsed. Only after
the holding time has elapsed the relay is released and reacts
again to status changes of the condition.
2.7.3 Technical data MI-100 (-MI1)
Table 25
Permissible voltage range
21 – 28.2 V DC
Power consumption
37 mA – 100 mA
Connection of DRY contacts 1 and 2
2 x 3 terminals
(NO / C / NC)
Connection of DRY contacts 3 and 4
2 x 3 terminals
(NO / C / NC)
LED indicator
4x white: “Relay ON”
yellow: “Failure”
green: “OK”
Table 26: Connection data for dry signal contacts
“NO / C / NC”
Voltage rating of the switching
contacts (C - NO)
max. 30 V DC
Voltage rating of the switching
contacts (C - NC)
max. 30 V DC
Current rating of the switching
contacts (C - NO)
max. 1 A
Current rating of the switching
contacts (C - NC)
max. 1 A
Switching capacity per switching
contact
30 W
Statement is
true
Statement is
NOT
true
Yes
No
No
Yes
Statement1
is true
Statement2
is true
Statement1
AND
Statement2 are true
Yes
Yes
Yes
Yes
No
No
No
Yes
No
No
No
No
Statement1
is true
Statement2
is true
Statement1
OR
Statement2 is true
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
No
No
No