Functions

3. Functions

3.1 Ventilation function

In order to use the SHEV

 

3 / 6 for ventilation, venti-

lation OPEN

 

/ CLOSE switches can be connected. 

Pressing both switches (OPEN

 

/ CLOSE) simulta-

neously causes the function STOP. The ventilation 
function can only be controlled during mains 
operation.

Kon-
fig.

SW1 
– 1

SW1 
– 2

SW1 
– 3

SW1 
– 4

Configuration ventilation switch

Remarks

Many different action behaviors can be allocated to 
the switches. Therefore see table 1 underneath. 

Figure 1: DIP switch SW1

Table

 

1: Matrix ventilation switch

1

OFF

OFF

OFF

OFF

Continuous OPEN

 

/ CLOSED

Delivery state

2

ON

OFF

OFF

OFF

OPEN and CLOSED with dead man 
function

Dead man function – the actuator 
will run as long as the vent button 
is pressed in OPEN or CLOSE.

3

OFF

ON

OFF

OFF

OPEN with dead man function

 

/  

CLOSED without

4

ON

ON

OFF

OFF

OPEN without dead man function

 

/

CLOSED with

5

OFF

OFF

ON

OFF

Gap ventilation

In case of ventilation, the actuators 
open for the programmed time.

6

ON

OFF

ON

OFF

Automatic ventilation CLOSED 

The system closes automatically 
after the expiration of the time.

7

OFF

ON

ON

OFF

Gap ventilation with automatic 
ventilation CLOSED

Combination of configuration 5  
and 6.

8

OFF

OFF

ON

ON

Programming mode for gap 
ventilation 

9

ON

OFF

ON

ON

Programming mode for  
automatic ventilation closed

10

ON

ON

ON

ON

Ventilation switch closed

Ventilation disabled

Summary of Contents for SHEV-3

Page 1: ...t to technical changes and errors All figures are exemplary Quick Guide SHEV 3 6 AP Only valid in combination with the attached sheet Safety instructions and warranty conditions Valid for following part numbers ST4 3140 SHEV 3 ST4 3141 SHEV 6 ST4 3146 SHEV 3 AP ST4 3151 SHEV 6 AP For further information please visit our product website short simon protec com sheven ...

Page 2: ... of the SHEV emergency switch 5 3 6 External output of messages 5 4 Mounting 5 4 1 Mounting plastic housing 5 4 2 Mounting steel sheet housing 6 4 3 Electrical connection 7 4 4 FAS Auto RESET function 8 4 5 Wire lengths 8 4 6 Motor cable monitoring by DD 100 8 5 Commissioning 9 5 1 Commissioning SHEV 3 6 plastic housing 9 5 2 Commissioning SHEV 3 AP 6 AP steel sheet housing 9 5 3 Troubleshooting 1...

Page 3: ...sures the function of the SHEV equipment for at least 72 hours The connection lines for SHEV emergency switch smoke detector Fire Alarm System FAS and actuators are monitored 2 Functional description SHEV 3 6 Smoke and Heat Exhaust Ventilation represent the compact control panel system main ly used in staircases for smoke extraction and daily ventilation It allows the direct connection of followin...

Page 4: ...ery state 2 ON OFF OFF OFF OPEN and CLOSED with dead man function Dead man function the actuator will run as long as the vent button is pressed in OPEN or CLOSE 3 OFF ON OFF OFF OPEN with dead man function CLOSED without 4 ON ON OFF OFF OPEN without dead man function CLOSED with 5 OFF OFF ON OFF Gap ventilation In case of ventilation the actuators open for the programmed time 6 ON OFF ON OFF Autom...

Page 5: ...d By pressing the RESET push button a second time the actuators will be triggered in closing direction 3 6 External output of messages For redirection of fault or other messages the SHEV 3 6 is equipped with two volt free relays or contacts In the factory setting contact 1 indicates ALARM and contact 2 indicates OK 4 Mounting 4 1 Mounting plastic housing Figure 2 Mounting points plastic housing SH...

Page 6: ...s plastic housing SHEV 6 4 2 Mounting steel sheet housing Figure 4 Mounting points steel sheet housing SHEV 3 AP Figure 5 Mounting points steel sheet housing SHEV 6 AP Figure 6 Connecting cable Mounting points housing Battery port Cable tie ...

Page 7: ... Vent Switch Motor 1 Motor 2 Motor fuses SHEV 3 T3 15A SHEV 6 T6 3A Wind Rain Emergency Button SW 1 ON OFF 1 2 3 4 5 6 7 8 9 10 Reset Alarm LED OK LED Alarm LED Fault L1 N PE S O G I G O S O O S S E LZ OK Y M RZ B1 RA L1 N PE Battery Battery 27kΩ 1 2 1 2 27kΩ A Z E A Z E DD 100 S G O O S O S 5 1 2 3 4 OK Y M B1 RA RZ GND M B1 RA RZ GND HE 081 HE 086 HE 080 HE 082 HE 087 FAS RM 3000 Vent Switch Act...

Page 8: ...e EOL diode terminators DD 100 are for the cable monitoring of the motor outputs They need to be installed in the junction box of the last actuator INFORMATION The use of shielded cables is recommended for the detection lines RM 2860 TH 4860 max 6 RM 3000 max 8 L1i L1o L2 L1i L1o L2 Smoke Detector Smoke Detector 27kΩ 27kΩ A Z E Ventilation Button A Z E A Z E Ventilation Button LZ E Wind Rain 5 2 1...

Page 9: ...t Battery backup see fig 4 5 on page 6 Figure 12 Battery Connection SHEV 3 AP steel sheet housing Figure 13 Battery Connection SHEV 6 AP steel sheet housing ATTENTION Only after the SHEV 3 6 AP has been commis sioned successfully and the permanent on site mains power supply is ensured the battery may be installed and connected INFORMATION An error message if the battery is disconnected may appear ...

Page 10: ...or 5 seconds to initialize the SHEV PE connection Fixing screws ATTENTION Due to the low loop current the insulation resistance of the monitored wires B1 B2 and B3 must be checked The insulation resistance must be 20 MΩ km manufacturer information otherwise wire interruptions will no longer be detected reliably INFORMATION The operating states of SHEV 3 6 AP can option ally be visualized with SIMO...

Page 11: ... Output voltage mains operation nominal 24 VDC Voltage range mains operation 23 0 VDC to 24 5 VDC Output voltage battery operation nominal 24 VDC Voltage range battery operation 21 VDC to 28 6 VDC Output current Iout short term operation Iout Imot1 Imot2 3 A SHEV 3 6 A SHEV 6 Power output non stop operation 50 W SHEV 3 100 W SHEV 6 Power output short term operation 73 5 W SHEV 3 145 W SHEV 6 Outpu...

Page 12: ...age range E Clamp 9 23 0 VDC to 24 5 VDC Current carrying capacity E Clamp 9 max 150 mA Connection information ventilation switch Output voltage range E Clamp 22 23 0 VDC to 24 5 VDC Connection information free input Input voltage range I Clamp 16 DO NOT USE Connection information volt free contacts NO C NC Voltage and current rating of the switching contacts 1 and 2 Clamp 32 on 31 33 Clamp 35 on ...

Page 13: ...SO 21927 9 prEN 12101 9 EN 12101 10 EPD acc ISO 14025 and EN 15804 Classification as per prEN 12101 9 Class D Classification as per EN 12101 10 Class A Environmental Class as per EN 12101 10 1 Control time of analog digital input Input digital RZ RA LZ Z A 500 ms Input analog B1 B2 B3 during mains operation 500 ms Input analog B1 B2 B3 during emergency power operation 2500 ms Technical information...

Page 14: ... clause Extend ed retention of title These are published by ZVEI Frankfurt If you are not familiar with these we would be happy to send them to you The agreements are also available for download at short simon protec com agben Passau is the established legal venue 7 4 Company addresses 7 4 1 System manufacturer SIMON PROtec Systems GmbH Medienstraße 8 D ದ 94036 Passau Tel 49 0 851 98870 0 Fax 49 0...

Reviews: