background image

User manual - INDICATOR TRS-10a 

Because of the  

TRS-10a

  is dedicated  for  

TRS

  system, all predefined  error

codes are compatible to error codes which may occur in this system. Values
transmitted to register 02h in „”

decimal mode”

 are limited. Higher byte can be

set to: 00h, 2Xh, 4Xh, 8Xh and Fxh, lower byte to 00h, 01h, 02h i 03h.

If user tray to write values other than mentioned above exception code 03h

occurs, and displayed value will not change.

In „

byte mode

” register 02h has different meaning.  In this mode it directly

drives segments of decade 2 (higher byte) and segments of decade 3 (lower

byte  - see Tab.5.1). Similarly as for register 01h, logical 1 on particular bit turn
on corresponding segment. In „

byte mode

” range of value stored to register

02h is 0000h ÷ FFFFh. 
After power switch on, if display has been set to „

decimal mode

” then higher 

byte of this register is cleared, and lower byte is set to previously set value 

(decimal point position is saved to EEPROM while power switching off), display
shows  "

- - - -

", as long as first correct MODBUS transaction will occur.

If before power off,  module has been set to „

byte mode

”, then after power on

content of register 02h is set to value 4040h, what is equal to displays of  "

-

"

on appropriate decades.

Register   03h

  -  Status   register.     Higher   byte   of  this   register   is  always   0.    If   display  is  in

decimal mode

”  lower byte of reg. 03h is a copy of higher byte of register

02h. Similarly it can get only limited values (see Tab. 5.2), and other values

causes exception code 03h. Module reacts to all changes of  lower byte of

reg. 03h as for changes of higer byte of reg. 02h. Changes of lower byte of

reg. 03h causes of automatical change of higher byte of reg. 02H - these two

bytes are interdependent.
If display is in „

byte mode

” , register 03h is cleared, and unavailable to write,

lower byte of reg 03h is not a copy of higher of reg. 02h. In this mode content

of register 03h is cleared after power switch on.

Register 04h

  -  Refresh period. After data writing to any of the registers, display   shows in

continuous mode value/warning according to registers 01h and 02h content.

Continuous displaying is continued as long as refresh period elapse. After that

displayed text starts to flashes, signalising that, defined time elapsed since

last   correct   MODBUS   transaction   with   display   module.   This   signalisation

allows   to   control   correctness   of   MASTER   system   operation.   Time   elapsed

from last correct MODBUS transaction is cleared after every data writing to

registers 01h - 05h and 20h of the display module – if particular register allows

writing in current mode (see descriptions of registers 03h and 05h). Refresh

period control  can be  switched  off, writing value FFFFh (65535) to register

04h,   or   set   any   other   value   from   range     100h   -   FFFEh   (256   -   65534)

expressed in seconds -  (from about 4 minutes to about 18 hours).

If user tray to write values other than mentioned above  exception code 03h

occurs,  content of register 04h will not be changed, and elapsed time will be

counted so on.

After power switch on, refresh time is temporarily off, until first correct write to

any of writeable registers. After that control of refresh time is continued witch

settings stored before power switch off (it can be permanently switched off)-

this set is saved in EEPROM. 

11

Summary of Contents for TRS-10a

Page 1: ...l INDICATOR TRS 10a Firmware v 3 00 or higher Designed for TRS system Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes with...

Page 2: ...6 3 EXAMPLES OF QUERY ANSWER FRAMES 14 7 FORCING OF 0XFF ADDRESS 19 Explanation of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operat...

Page 3: ...ed off and disconnected from the power supply prior to starting installation of troubleshooting in the case of malfunction Neighbouring and mating equipment must meet the requirements of appropriate s...

Page 4: ...9 mm height red high bright Number of modules in 1 network maximum 127 Communication interface Baud rate RS 485 8N1 Modbus RTU 9600 bit sec Data memory non volatile memory EEPROM type Protection level...

Page 5: ...ducted with a disconnected power supply 4 1 UNPACKING After removing the unit from the protective packaging check for transportation damage Any transportation damage must be immediately reported to th...

Page 6: ...etc Carelessly executed assembly can increase the risk of electric shock Due to possible significant interference in industrial installations appropriate measures assuring correct operation of the uni...

Page 7: ...le in the network must be terminated with 100 150 Ohm resistor Figure 4 4 Connection of the module to the network 7 1 2 3 4 DATA DATA RS 485 Us Us 9 12V DC GND LED indicator force address 0xFF switch...

Page 8: ...nts available to the user Pay attention to the ambient temperature in the room where the unit is operating Excessively high temperatures cause faster ageing of the internal components and shorten the...

Page 9: ...re value out of this range an error occur device answers with exception code 03 improper data value and displayed value will not change After switching power on if display has been set to decimal mode...

Page 10: ...t decade If value 0003h will be written to reg 02h then value 0 124 will be displayed Additionally higher byte of register 02h decides about interpretation of reg 01h value If higher byte of register...

Page 11: ...ower byte of reg 03h as for changes of higer byte of reg 02h Changes of lower byte of reg 03h causes of automatical change of higher byte of reg 02H these two bytes are interdependent If display is in...

Page 12: ...module These addresses can be changed at any time using proper MODBUS commands or can be forced to be reset to 0xFF value using module internal momentary switch to enhance system installation process...

Page 13: ...ying status physical copy of higher byte of 02h register higher byte always 0 Byte mode always 0 can not be written 04h Yes 100h FFFFh Refresh period 05h Yes 00h 01h Operation mode 20h Yes 0h FFh Devi...

Page 14: ...address 1 All values are represent hexadecimal Field description ADDR Device address on Modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byt...

Page 15: ...A H L CRC L H 01 06 00 20 00 02 09 C1 3 Turning on of decimal mode ADDR FUNC REG H L DATA H L CRC L H 01 06 00 05 00 00 99 CB The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01 0...

Page 16: ...nt 6 Changing of decimal point position ADDR FUNC REG H L DATA H L CRC L H 01 06 00 02 00 02 A9 CB The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 02 00 02 A9 CB Display...

Page 17: ...s the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 05 00 01 58 0B Display content 10 Displaying of text Port Because in this mode segments are driven directly by bits of register 01h and 02h it...

Page 18: ...H L CRC L H 01 06 00 02 5C 73 50 EF Display content 11 Read of the registers 1 to 5 in one message example of reading a number of registries in one frame ADDR FUNC REG H L DATA H L CRC L H 01 03 00 01...

Page 19: ...s is implemented in Piggy Soft application as network configuration process To force address of device to value 0xFF turn module power supply and wait until it s LED indicator flashes every 10 second...

Page 20: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: