6.2. 

 

     READING  OF THE MEASUREMENT RESULT

 

 

Averaged (filtered) result of temperature measurements is available in holding register 

no.   01h.   Reading   of  the   result   may  be  done   using  MODBUS  RTU  function   03h.   If   single 

holding   register   is   being   readed     (01h),   then   module   signalises   any   alarm   situation   by 

exception code  (different than standard answer frame – see example 1). If group of holding 

registers (contain status register 02h) or only status register (02h) is being readed, then device 

transmits standard answer with current measurement status.

6.3. 

 

     TRANSMISSION ERRORS DESCRIPTION

 

 

If an error occurs  while write or read of  single register, then the device sends an error 

code according to Modbus RTU specifications (example message no 1).

Error codes:

00h

- measurement correct (this error code can be readed from status registers only),

01h

- illegal function (only functions 03h and 06h are available),

02h

- illegal register address

03h

- illegal data value

10h

- water inside module,

20h

- temperature sensor damaged,

40h

- exceed of lower border of input range ( -50°C, sensor damage possible),

80h

- exceed of upper border of input range (550°C, sensor damage possible),

A0h

- PT-100 line broken/opened,

60h

- PT-100 line short circuit

10h, 20h, 40h, 60h, 80h, and A0h codes can appear only during reg. 01h is reading by 03h 

function (read of a single register).

Error code can be a logical sum of two or more errors. Sensor failure usually do not 

breaks   actualisation   of   measurement   results,   and   current   result   can   be   readed 

using   multi   register   mode   (   in   single   register   mode     the   modules   send   off   the 

exception codes).

6.4. 

 

     EXAMPLES OF QUERY/ANSWER FRAMES

 

 

Examples apply for device with address 1. All values are represent hexadecimal.

Field description:
ADDR

Device address on Modbus network

FUNC

Function code

REG H,L

Starting address (address of first register to read/write, Hi and Lo byte)

COUNT H,L

No. of registers to read/write (Hi and Lo byte)

BYTE C

Data byte count in answer frame

DATA H,L

Data byte (Hi and Lo byte)

CRC L,H

CRC

 

error check (Hi and Lo byte)

12

Summary of Contents for TRS-02a

Page 1: ...RANSDUCER TRS 02a Firmware v 2 04 or higher Input type Pt100 Designed for TRS system Read the user s manual carefully before starting to use the unit or software Producer reserves the right to impleme...

Page 2: ...ISSION ERRORS DESCRIPTION 12 6 4 EXAMPLES OF QUERY ANSWER FRAMES 12 7 FORCING OF 0XFF ADDRESS 15 Explanation of symbols used in the manual This symbol denotes especially important guidelines concernin...

Page 3: ...be switched off and disconnected from the power supply prior to starting installation of troubleshooting in the case of malfunction Neighbouring and mating equipment must meet the requirements of appr...

Page 4: ...100 type with automatic connection recognition 2 3 or 4 wires Measurement range 50 C up to 550 C Measurement error 0 2 Measurement wires resistance max 20 every wire Number of modules in 1 network max...

Page 5: ...safety requirements on page 3 prior to starting the installation All installation works must be conducted with a disconnected power supply 4 1 UNPACKING After removing the unit from the protective pac...

Page 6: ...overs and sealing packing protecting against water intrusion pay special attention to their correct tightening or clamping In the case of any doubt consider using additional preventive measures covers...

Page 7: ...terminals Figure 4 3 Location of elements inside the module case Last module in the network must be terminated with 100 150 Ohm resistor Figure 4 4 Connection of the module to the network 7 max 2 mm...

Page 8: ...connected to the device in typical 4 wire circuit Figure 4 6 a 3 wire circuit Figure 4 6 b or 2 wire circuit Figure 4 6 c Due to precision of measurement 4 wire circuit is recommended If 2 wire circu...

Page 9: ...nit is operating Excessively high temperatures cause faster ageing of the internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with sol...

Page 10: ...All settings are stored in non volatile EEPROM memory and available under fixed register numbers LED indicator is installed in the module mainboard it indicates following situations normal operation...

Page 11: ...0 1 C U2 code no decimal point included e g value 155 means shifting of 15 5 C 07h 08h see descr Calibration registers do not change WARNING modification of these registers causes recalibration of mo...

Page 12: ...02h illegal register address 03h illegal data value 10h water inside module 20h temperature sensor damaged 40h exceed of lower border of input range 50 C sensor damage possible 80h exceed of upper bo...

Page 13: ...int Decimal point position can be read from reg 03h b The answer if an error occur ADDR FUNC ERROR CRC L H 01 83 40 40 C0 ERROR error code 40h bottom border of the measurement range is exceeded 2 Read...

Page 14: ...a The answer we assume that input signal is not out of range ADDR FUNC BYTE C DATA H1 L1 DATA H2 L2 CRC L H 01 03 04 00 C1 00 00 AB CF DATA H1 L1 reg 01h 193 measurement value 19 3 C DATA H2 L2 reg 0...

Page 15: ...iguration process To force address of device to value 0xFF turn module power supply and wait until it s LED indicator flashes every 10 second Next press internal switch button and hold it at least 4 s...

Page 16: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: