User manual - METER SRT-N118
Register Write
Range
Register description
2Fh
Yes
0 ÷ 1
“
Edit
” parameter (numerical parameters edit mode);
0
- „
dig
” mode;
1
- „
SLid
” mode
30h
Yes
-999 ÷ 9999 “
SEtP
” parameter in “
rEL1
” menu, no decimal point included
31h
Yes
-999 ÷ 999
“
HySt
” parameter in “
rEL1
” menu, no decimal point included
32h
Yes
0 ÷ 5
“
modE
” parameter in “
rEL1
” menu:
0
- “
noAC
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modb
” mode
33h
Yes
0 ÷ 999
“t on”
parameter in
“rEL1”
menu, expressed in tenth of seconds or
tenth of minutes depend on
“unit”
parameter - register no. 35h)
34h
Yes
0 ÷ 999
“toFF”
parameter in
“rEL1”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 35h)
35h
Yes
0 ÷ 1
“unit”
parameter in
“rEL1”
menu:
0
- seconds;
1
- minutes
36h
Yes
0 ÷ 2
“AL”
parameter in
“rEL1”
menu:
0
- no changes;
1
- on;
2
- off
37h
Yes
-999 ÷ 9999 “
SEt2
” parameter in “
rEL1
” menu, no decimal point included
38h
Yes
-999 ÷ 9999 “
SEtP
” parameter in “
rEL2
” menu, no decimal point included
39h
Yes
-999 ÷ 999
“
HySt
” parameter in “
rEL2
” menu, no decimal point included
3Ah
Yes
0 ÷ 5
“
modE
” parameter in “
rEL2
” menu:
0
- “
noAC
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modb
” mode
3Bh
Yes
0 ÷ 999
“t on”
parameter in
“rEL2”
menu, expressed in tenth of seconds or
tenth of minutes depend on
“unit”
parameter - register no. 3Dh)
3Ch
Yes
0 ÷ 999
“toFF”
parameter in
“rEL2”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 3Dh)
3Dh
Yes
0 ÷ 1
“unit”
parameter in
“rEL2”
menu:
0
- seconds;
1
- minutes
3Eh
Yes
0 ÷ 2
“AL”
parameter in
“rEL2”
menu:
0
- no changes;
1
- on;
2
- off
3Fh
Yes
-999 ÷ 9999 “
SEt2
” parameter in “
rEL2
” menu, no decimal point included
50h
Yes
0 ÷ 1
“
modE
” parameter in “
HOLd
” menu (type of detected changes):
0
- peaks;
1
- drops
51h
Yes
0 ÷ 9999
“
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included)
52h
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks' (or drops')
display time expressed in seconds
53h
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
54h
Yes
0 ÷ 1
“
H r1
” parameter in “
HOLd
” menu
:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
55h
Yes
0 ÷ 1
“
H r2
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
37