User manual - METER SRT-N118-XA
The state of relay output while the input value exceeds the
border values
(points A, B, C,
D) is described by parameter
“modE”.
The relay can be turned on (
“modE”
=
”on”
), or
turned off (
“modE”
=
”oFF”
) when input signal value is contained in
zone A
(Figure 6.4 a).
The parameter
“AL”
allow user to set the relay output behaviour in critical situations (e.
g. Input values exceeds
permissible measurement range
)
.
User can select that the relays
will be turned on, turned off,or not changed in critical situations.
All parameters connected with relay outputs are described in paragraph
”rEL1” menu
.
6.3.2.
Two thresholds mode
Objaśnienie:
A, B, C, D, E
- points where measured signal exceeds border values (expected value ± allowed deviation)
B
ON
,
B
OFF
,
C
ON
,
C
OFF
,
E
ON
,
E
OFF
- relays state changes moments: (for
“t on”
> 0,
“toFF”
> 0)
t
A
,
t
B
,
t
C
,
t
D
,
t
E
-
time periods while input signal is in zone A or zone B
Figure 6.5. Principle of LED/relay output operation for two thresholds mode
Figure 6.5 presents the principle of relay outputs operation for two thresholds mode, and
an example values of other parameters. In this mode parameter
“SEt2”
is accessible in
common with
“SEtP”
, this parameter describes a second threshold of the relay output. The
parameters
“HYSt”
,
“modE”
,
“t on”
,
“toFF”
,
“unit”
and
“AL”
are connected with both
21
E
OFF
“SEtP”
or
“SEt2”
parameter
“HYSt”
parameter
measure
d signal
displayed value
time
time
time
A
B
C
D
relay state
(
modE
=
in
t on
= 0
toFF
= 0)
relay state
(
modE
=
in
t on
> 0
toFF
> 0)
t
A
t
C
t
D
B
ON
relay state
(
modE
=
out
t on
= 0
toFF
= 0)
relay state
(
modE
=
out
t on
> 0
toFF
> 0)
“toFF”
parameter
“t on”
parameter
B
OFF
E
ON
time
time
closed
open
a)
b)
c)
d)
e)
open
closed
open
open
closed
closed
“t on”
parameter
“toFF”
parameter
zone A
zone B
“HYSt”
parameter
zone B
C
OFF
C
ON
E
“t on”
parameter
“toFF”
parameter
t
B
t
E