background image

User manual - METER SRT-N118-XA 

“SEtP”

  and  

“SEt2”  

thresholds. While the controlling process, the relay output changes his 

state depends of both 

“SEtP”

 and 

“SEt2” 

thresholds in similar way as it was described in one 

threshold mode. 

If two threshold mode is used,  

“modE”

 parameter defines state of the relay output when 

the input value occurs in a particular zone defined by 

border values

 of both 

thresholds

. The 

relay can be turned on if the input value is contained in 

zone A 

 (

“modE” 

”in”

) or 

zone B 

(

“modE” 

”out”

) and turned off if it is contained in the second one

 

(Figure 6.5).

The sequence of thresholds 

“SEtP”

 and  

“SEt2” 

can be

 

set in any order, due to the 

control   of   relay   outputs   is   done   depend   on   difference   between   thresholds   values 
(

zone A 

) and outside of threshold values (

zone B

).

7. 

   DEVICE PROGRAMMING

 

 

The   device   menu   allow   user   to   set   all   parameters   connected   to   operation   of 

measurement input, control modes, critical situations behaviour, communication via RS-485 

and  access   settings.  The meaning  of  the  particular  parameters  is   described  in  paragraph 

MENU DESCRIPTION

.

Some of the parameters can be accessed without menu entering (quick  view mode). 

After pressing  

[^]

  or  

[v]

  button,   name of the threshold (e.g.

”rEL1”

) and his value will be 

displayed on the display in alternating mode. If 

[^]

 or 

[v] 

will be pressed in 5 sec again, the 

next threshold will be displayed, else the device comes back to the measurement mode. If a 

free access

  is enabled (see description of  

”SECu” menu

), user can change the value of 

particular threshold pressing button  

[ENTER]

 (see: 

 PARAMETERS EDITION

). 

If particular parameter has been changed and confirmed in quick view mode, its 

new value is displayed in alternating mode with parameter name by few seconds. 

Confirmed changes may be checked or user can switch viewed parameter pressing 

[^] 

or 

[v]

 button.

7.1. 

 

 PROGRAMMING MENU

 

 

To enter main menu (being in the measurement mode) operator must to press and hold 

at least 2 sec. 

[ESC/MENU] 

button.

If the user password is defined (see parameter 

“Scod“

 

menu 

”SECU”

), operator have 

to enter correct one before proceeding to menu options . Entering of the passwords is similar 
to the edition of numeric parameters

 

(see: 

PARAMETERS EDITION

 

)

,

 however presently editing 

digit is showed only on the display, other digits are replaced by “-” sign.

After entering of last digit of the password first menu position will be displayed (if the password  
is correct) or warning ”

Err

” in other case.

Pay attention when device parameters are being changed. If it is possible, turn off 

controlled installation (machine).

22

i

i

!

Summary of Contents for SRT-N118-XA

Page 1: ...XA Firmware v 6 00 or higher Input type TC K S J T N R B E Wall mounting case IP 67 Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implemen...

Page 2: ...ROGRAMMING MENU 22 7 2 PARAMETERS EDITION 23 7 2 1 Numeric parameters digit change mode 23 7 2 2 Numeric parameters slide change mode 23 7 2 3 Switch parameters LIST type 24 7 3 MENU DESCRIPTION 24 7...

Page 3: ...ing to this manual local safety and EMC regulations If the device is equipped with PE connector it should be connected to PE wire Otherwise PE wire should be connected to GND connector The unit must b...

Page 4: ...nsated automatically The device has additional measurement range 10 90mV mainly for diagnostics of measurement circuits Being in this range unit displays direct voltage connected to its input without...

Page 5: ...1300 C R 50 C 1768 C B 250 C 1820 C E 200 C 1000 C Voltage 10mV 90mV Measurement accuracy 0 1 25 C one digit Accuracy of cold ends temperature compensation 1 C Temperature stability 50 ppm C Outputs r...

Page 6: ...85 8N1 and 8N2 Modbus RTU not separated Baud rate 1200 bit s 115200 bit s Display depending on version LED 4 digit 20mm height red or LED 4 digit 20mm height green Data memory non volatile memory EEPR...

Page 7: ...to take full advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations Read the basic safety requirements on page 3 prior to starti...

Page 8: ...sidered The fitter is responsible for executing the installation according to this manual local safety and EMC regulations The unit is not equipped with an internal fuse or power supply circuit breake...

Page 9: ...nterference in industrial installations appropriate measures assuring correct operation of the unit must be applied To avoid the unit of improper indications keep recommendations listed below Avoid ru...

Page 10: ...a for big connectors 1 to 6 b for small connectors 7 to 16 Figure 4 3 Method of connecting cables to the clamping connectors All connections must be made while power supply is disconnected Figure 4 4...

Page 11: ...x 30V DC Imax 30mA Pmax 100mW Power supply depending on version TC GND GND 3 4 1 2 14 15 16 5 6 12 11 10 9 8 7 13 Uo n c R1 GND DATA DATA RS 485 option 24V 5 10 Imax 100 mA PE Power supply depending o...

Page 12: ...485 option 24V 5 10 Imax 100 mA PE Passive isolated current output 4 20mA option Power supply depending on version TC GND GND 3 4 1 2 14 15 16 5 6 12 11 10 9 8 7 13 Uo n c GND DATA DATA RS 485 24V 5...

Page 13: ...GND DATA DATA RS 485 option 24V 5 10 Imax 100 mA PE Power supply depending on version TC GND GND ACTIVE voltage output option 1 2 14 15 16 5 6 12 11 10 9 8 7 13 3 4 Uo n c GND DATA DATA RS 485 24V 5...

Page 14: ...ctromagnets motors etc it is required to use additional suppression circuit typically capacitor 47nF min 250VAC in series with 100R 5W resistor connected in parallel to relay terminals or better direc...

Page 15: ...current output only Figure 4 16 Example of passive current outputs connection for device with passive current output only 15 6 5 8 7 OC1 Uo voltage input 24V Logic controller 6 5 8 7 R 2k2 LED 10 mA...

Page 16: ...ter ageing of the internal components and shorten the fault free time of the unit s operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small amoun...

Page 17: ...e ID and software version are showed on the display next the controller goes to the measurement mode 6 1 MEASUREMENT MODE In the measure mode the measurement results are displayed on the display If th...

Page 18: ...detection of the peak can be done if the measured signal raises and drops of value at least equal to parameter PEA Detected peaks are displayed during the time defined by parameter timE If a new peak...

Page 19: ...hresholds values If one threshold is used Figure 6 2 the relay can be turned on modE on or off modE oFF when the input signal value is contained in zone A If two thresholds are used Figure 6 3 the rel...

Page 20: ...to 0 then the relay state will be changed as soon as input value exceeds any of the border values see points A and C Figure 6 4 a b c If values of t on or and toFF are positive then relay state will b...

Page 21: ...moments for t on 0 toFF 0 tA tB tC tD tE time periods while input signal is in zone A or zone B Figure 6 5 Principle of LED relay output operation for two thresholds mode Figure 6 5 presents the princ...

Page 22: ...n name of the threshold e g rEL1 and his value will be displayed on the display in alternating mode If or v will be pressed in 5 sec again the next threshold will be displayed else the device comes ba...

Page 23: ...nge of current position flashing digit or the sign Short pressing of the ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after that question SEt i...

Page 24: ...e change of value acceleration deceleration direction change While editing switch parameter selection of switch parameter If numerical parameter is being edited a short press of ENTER button change ed...

Page 25: ...in or out value Threshold is the medium value of relay hysteresis HYSt hysteresis of relay range 0 999 Full hysteresis of the relay is equal to 2x HYSt parameter The relay state can change when an inp...

Page 26: ...arameter is set by unit parameter toFF turn off delay time the relay is turned off with delay equal toFF if the input value exceeds appropriate border value defined with threshold and hysteresis at le...

Page 27: ...can be set to values thermocouple type measurement range tc K 200 C 1370 C tc S 50 C 1768 C tc J 210 C 1200 C tc t 200 C 400 C tc n 200 C 1300 C tc r 50 C 1768 C tc b 250 C 1820 C tc E 200 C 1000 C v...

Page 28: ...d via RS 485 interface For active voltage output oFF voltage output disabled 0 5 voltage output enabled with 0 5V mode 1 5 voltage output enabled with 1 5V mode 0 10 voltage output enabled with 0 10V...

Page 29: ...e on page 35 of the DISPLAY VALUES CALCULATION paragraph the procedure of the analogue outputs determining is presented in details AL this parameter determines the behaviour of analogue output if any...

Page 30: ...tputs R1 R2 operation mode rEAL relay LED operates depend on the current value HOLd relay LED operates depend on the peak drop value HOUt current output operation mode rEAL current output operates dep...

Page 31: ...the device If the delay will be greater than the value of mbtO parameter the relays and the current output which are controlled via RS 485 interface will set to alert state see OUtP menu and rEL1 menu...

Page 32: ...ore the factory settings of the device To get the access to this option special password is required 5465 next the device displays acknowledge question SEt Press ENTER to acknowledge the restoring of...

Page 33: ...Measurement mode ENTER MENU ESC MENU ESC inPt ENTER MENU ESC ENTER ENTER MENU ESC SEtP SEt2 HYSt modE t on toFF unit AL Parameter edition See next page MENU ESC bri ENTER MENU ESC ENTER Parameter edi...

Page 34: ...eter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud mbAc mbtO rESP Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Scod A r1 A r2 See previous page ENTER MENU ESC ENTER ENTER MENU ESC mod...

Page 35: ...e 28 Iout 30 0 10 0 20 0 10 0 16 mA 4 mA 2 16 4 36 mA Calculated Iout exceeds the output working range 3 21 mA so current output will generate current equal to the upper border of range defined by par...

Page 36: ...Peak drop value no decimal point 08h No 0 50 Temperature inside device housing expressed by 1 C 10h Yes 0 8 tyPE parameter in InPt menu input type 0 thermocouple input K 1 thermocouple input S 2 therm...

Page 37: ...enth of minutes depend on unit parameter register no 35h 35h Yes 0 1 unit parameter in rEL1 menu 0 seconds 1 minutes 36h Yes 0 2 AL parameter in rEL1 menu 0 no changes 1 on 2 off 37h Yes 999 9999 SEt2...

Page 38: ...es 0 2 AL parameter in OUtP menu current output value on critical exception 0 no change 1 22 1 mA 2 3 4 mA 1 these registers are active only if device is equipped with current output 2 after writing t...

Page 39: ...device address 01h ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 01 00 01 D5 CA a The answer we assume that the measure result is not out of range ADDR FUNC BYTE C DATA H L CRC L H 01 03 02 00 FF F8 0...

Page 40: ...ce do not reply to BROADCAST type messages 5 Read of the registers 1 2 and 3 in one message example of reading a number of registries in one frame ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 01 00 03...

Page 41: ...5 HYSt Hysteresis of relay R2 0 0 25 modE Operation mode of relay R2 on 25 t on Turn on delay of relay R2 0 0 26 toFF Turn off delay of relay R2 0 0 26 unit Unit of t on toFF parameters of relay R2 SE...

Page 42: ...rrent output control rEAL 30 Settings of access to the configuration parameters SECu menu A r1 Permission to changes of relay R1 threshold without of the user password knowledge on 30 A r2 Permission...

Page 43: ...User manual METER SRT N118 XA 43...

Page 44: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: