User manual - METER SRT-147-XA
6.
PRINCIPLE OF OPERATION
After turning the power supply on, device ID and software version are showed on the
display, next the controller goes to the measurement mode.
6.1.
MEASUREMENT MODE
In the measure mode, the measurement results, are displayed on the display. If the result
of measurement exceeds the
permissible measurement range
, warning
”-Hi-”
or
”-Lo-”
is
displayed rather than
calculated result
,
depends on exceeded value.
In the measurement mode user can check main thresholds values. After pressing
[^]
or
[v]
button, name of the threshold (e.g.
”rEL1”
) and his value will be displayed on the display
in alternating mode. If
[^]
or
[v]
will be pressed in 5 sec again, the next threshold will be
displayed, else the device comes back to the measurement mode. If a
free access
is enabled
(see description of
”SECu” menu
), user can change the value of particular threshold pressing
button
[ENTER]
(see:
PARAMETERS EDITION
).
All accessible parameters can be changed by entering the menu (see:
DEVICE
PROGRAMMING
). Use the local keyboard or the remote controller to do it. (Note: all
parameters can be remote changed via RS-485 interface).
Configuration of the device (via menu or RS-485 interface)
do not stops measures
.
6.2.
DETECTION OF THE PEAK VALUES
controller is equipped with peaks detection function. It can detect a
peaks of the input signal and display their values. Presets connected with this function are
placed in
”HOLd”
menu (see description of
”HOLd” menu
). The detection of the peak can be
done if the measured signal raises and drops of value at least equal to parameter
”PEA”
.
Detected peaks are displayed during the time defined by parameter
”timE”
. If a new peak will
be detected while one is displayed, this new peak will be displayed and display time counter
will be cleared
(Figure 6.1). If no peaks are detected while time
”timE”
elapses
,
device starts
to show the current value of input signal again. If „
HdiS
”=”
HOLD
” then setting parameter
"timE"
=
0.0
causes holding peak value until
[ESC]
button is pressed.
If „
HdiS
”=”
rEAL
” then
value
"timE"
=
0.0
means no holding. Displaying peak value is signalized by flashing most right
decimal point.
The relays/LEDs and the current output can be controlled depend on the current value of
input signal or the peak value (see
”HOLd” menu
).
14
i