User manual - METER SRP-94
Current input resistance
< 65
Ω
(typical 55
Ω
)
Accepted prolonged input overload: 20%
Voltage input
0÷5 V, 1÷5 V, 0÷10 V, 2÷10 V
Voltage measurement accuracy
± 0,1% @ 25°C; ± one digit (for 0÷10 V range)
Voltage input resistance
> 50 k
Ω
Accepted prolonged input overload: 20%
Sensor power supply output
24V +5%, -10% / max. 100 mA, stabilized
Relay output
0, 2 or 4 NO, 1A/250V AC (cos
ϕ
= 1)
OC-type output
0, 2 or 4; 30mA / 30VDC / 100mW
Active current output
(optional, for two relays or two
OC-type output version only)
range max. 0 ÷ 24 mA
Load resistance max.
700
Ω
Passive isolated current output
(optional, for two relays or two
OC-type output version only)
range max. 2.8 ÷ 24 mA
Supply voltage
Us = 9.5 ÷ 36V
Load resistance max.
(Us – 9.5V) / 24mA [k
Ω
]
Active voltage output
(optional, for two relays or two
OC-type output version only)
range max. 0 ÷ 11V
Load resistance min.
2000
Ω
Temperature stability
50 ppm / °C
Display range
-999 ÷ 9999, plus decimal point
Communication interface
RS 485, 8N1 and 8N2, Modbus RTU,
not separated
Baud rate
1200 bit/s ÷ 115200 bit/s