User manual - METER SRP-94-XC
•
If parameter „
AL
” = „
on
”, the relay will be turned on in the critical situations,
even if his parameter
“modE”
=
”noAC”.
7.3.2.
“bEEP” menu
This menu contains options connected with acoustic signal :
"
AL
”
- if this parameter is set to “
on
”, any critical situation causes by acoustic signal
"
r1”
- if this parameter is set to “
on
”, activation of relay
R1
causes by acoustic signal
"
r2
"
- if this parameter is set to “
on
”, activation of relay
R2
causes by acoustic signal
"
r3
"
- if this parameter is set to “
on
”, activation of relay
R3
causes by acoustic signal
"
r4
"
- if this parameter is set to “
on
”, activation of relay
R4
causes by acoustic signal
Acoustic signal (turned on by e.g. relay ) can be turned off by pressing of any
button
7.3.3.
“inPt” menu
This menu presets the measurement input:
“
tYPE
"
- type of the input / sensor. This parameter can be set to values:
”
60
”,
“
75
”, ”
100
”,
“
150
”
- voltage inputs expressed in mV.
Displayed values are defined by parameters
“Lo C”
,
”Hi C”
(or by user defined
characteristic points) and parameter
”Pnt”
.
”CHAr”
- this option presets type of the conversion characteristic, and can be set to:
”Lin”
- linear
“Sqr”
- square
“Sqrt”
- square root
When one of those characteristics is chosen display
range is defined by
“Lo C”
and
“Hi C”
.
“USEr”
- user defined characteristic. Maximal length 20 points. Every point is
defined by user. Adding, Editing and Deleting of points is done by options
„
AddP
”, „
EdtP
”, „
dELP
” („
InPt
” menu) respectively.
If user defined characteristic is selected, and if number of defined points is lower
than 2 then warning ”
Errc
” is displayed in measurement mode.
The process of displayed result calculation is described in details in
DISPLAY VALUES
CALCULATION
paragraph.
”FiLt”
- this parameter sets filtration rate. It can be set to values from 0 (no filtration ) to 5
(strongest filtration – time window about 2 sec).
”Pnt”
- decimal point position. It can be set to one of:
“ 0”
,
“ 0.0”
,
“ 0.00”
,
“0.000”
Decimal point position is changed by
[^]
,
[v]
buttons.
25