User manual - METER SRP-457
The parameter
“AL”
allow user to set the relay output behaviour in critical situations (e.
g. Input values exceeds
permissible measurement range
)
.
User can select that the relays
will be turned on, turned off,or not changed in critical situations.
All parameters connected with relay outputs are described in paragraph ”rEL1” menu.
6.3.2.
Two thresholds mode
Objaśnienie:
A, B, C, D, E
- points where measured signal exceeds border values (expected value ± allowed deviation)
B
ON
,
B
OFF
,
C
ON
,
C
OFF
,
E
ON
,
E
OFF
- relays state changes moments: (for
“t on”
> 0,
“toFF”
> 0)
t
A
,
t
B
,
t
C
,
t
D
,
t
E
-
time periods while input signal is in zone A or zone B
Figure 6.7. Principle of LED/relay output operation for two thresholds mode
Figure 6.7 presents the principle of relay outputs operation for two thresholds mode, and an
example values of other parameters. In this mode parameter
“SEt2”
is accessible in common
with
“SEtP”
, this parameter describes a second threshold of the relay output. The parameters
“HYSt”
,
“modE”
,
“t on”
,
“toFF”
,
“unit”
and
“AL”
are connected with both
“SEtP”
and
“SEt2”
thresholds. While the controlling process, the relay output changes his state depends
of both
“SEtP”
and
“SEt2”
thresholds in similar way as it was described in one threshold
mode.
If two threshold mode is used,
“modE”
parameter defines state of the relay output when
18
E
OFF
“SEtP”
or
“SEt2”
parameter
“HYSt”
parameter
measure
d signal
displayed value
time
time
time
A
B
C
D
relay state
(
modE
=
in
t on
= 0
toFF
= 0)
relay state
(
modE
=
in
t on
> 0
toFF
> 0)
t
A
t
C
t
D
B
ON
relay state
(
modE
=
out
t on
= 0
toFF
= 0)
relay state
(
modE
=
out
t on
> 0
toFF
> 0)
“toFF”
parameter
“t on”
parameter
B
OFF
E
ON
time
time
closed
open
a)
b)
c)
d)
e)
open
closed
open
open
closed
closed
“t on”
parameter
“toFF”
parameter
zone A
zone B
“HYSt”
parameter
zone B
C
OFF
C
ON
E
“t on”
parameter
“toFF”
parameter
t
B
t
E