User manual - COUNTER SLIK-94
Allowable connection methods and counter configurations are showed in table 6.1.
used
counting input
”Funct”
parameter
“Pr inP”
parameter
state of
”C” input
B
”A - B”
”dirEct”
no active
B
”A - B”
other than ”dirEct”
any
A
”A - B”
”dirEct”
active
A or B
”A + B”
”dirEct”
active
A and B
”quAd 1” or ”quAd 4”
”dirEct”
no active
A and B
”quAd 1” or ”quAd 4”
other than ”dirEct”
any
B and A
”quAd 1” or ”quAd 4”
”dirEct”
active
Tab. 6.1. Possible configurations while use device as a batcher
Amount of poured fluid can be changed by parameter
“oFFSEt”
, which is showed first in
quick view mode, while parameter
“A oFFS” = “on”
(see page 33). Proposed in example
system is showed in Figure 6.2, and proposed circuit diagram in Figure 6.3.
More details of this example are described on page 36.
Figure 6.2. Proposed system
17
Flow detector
main valve,
controlled by relay R1
additional valve,
controlled by relay R2
pulses to „B“ input
tank