![Simex SLIK-94 User Manual Download Page 36](http://html1.mh-extra.com/html/simex/slik-94/slik-94_user-manual_1275347036.webp)
User manual - COUNTER SLIK-94
8.
EXAMPLES OF PRESCALER PARAMETERS CALCULATION
Problem:
to measure length of the line with assumed precision.
Essential data
:
- number of pulses per revolution given by sensor
- circumference of measurement circle
- assumed measurement unit and resolution (mm, cm, dm, m).
Example 1
Data:
- circumference of measurement circle:
25
cm
- number of pulses:
100
pulses/revolution
- unit
cm,
resolution
1 cm
25 cm = 1 revolution = 100 pulses
Settings :
mul = “25”
div = “100”
oFFset = “0”
point = “0.”
Example 2
Data:
- circumference of measurement circle:
50
cm
- number of pulses:
100
pulses/revolution
- unit
dm
, resolution
0,1 dm
50 cm = 5 dm = 1 revolution = 100 pulses
Settings:
mul = “50”
div = “100”
oFFset = “0”
point = “0.0”
Example 3
- counter
SLIK-73
used in batcher function (see: Figure 6.2, 6.3)
Data:
–
flow meter:
100
pulses/ L
–
main valve flow (valve 1): about
10
L / sec.
–
additional valve flow (valve 2): about
1
L / sec.
–
measurement precision: up to
0,1
L.
–
valve is open while relay are closed
Settings:
mul = “1”
div = “10”
Point = “0.0”
relay R1 threshold = ”6.0”
- we assume that, since beginning of start of main valve
closing, it will flow about 3 L of water
“A rEL1”
=
“on”
- access to threshold edition without password
relay R2 threshold = ”3.0”
- we assume that, since beginning of start of additional
valve closing, it will flow about 0.3 L of water
“A rEL2”
=
“on”
-
access to threshold edition without password
“A oFFS”
=
“on”
-
access to offset edition without password
“Funct”
=
“A - B”
-
input
”B”
is used
programmable input
”C”
- non active if
”Pr inP”
=
”dirEct”
, or any if
”Pr inP”
is set to
other value setting