User manual - COUNTER SLE-73
Device do not reply to BROADCAST-type messages.
4. Read of the displayed value (higher word):
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
01
00
01
D5
CA
Response, while normal operation (no errors):
ADDR
FUNC
BYTE C
DATA H,L
CRC L,H
01
03
02
00
00
B8
4C
DATA H, L - 0000h = 0, higher word of displayed value = 00
5. Read of the displayed value (high and low word),
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
01
00
02
95
CB
Response, while normal operation (no errors):
ADDR
FUNC
BYTE C
DATA H1,L1
DATA H2,L2
CRC L,H
01
03
04
00
00
00
57
BB
CD
DATA - 00000057h = 87, displayed value = 87
6. Settings of the programmable inputs parameters, “Pr InP”=”rESEt”
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
11
00
01
18
0F
The answer (the same as the message):
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
11
00
01
18
0F
26