User manual

COUNTER

SLE-73

Firmware: v.4.00 or higher

Input type: pulse

Low-cost counter

Read the user's manual carefully before starting to use the unit or software. 

Producer reserves the right to implement changes without prior notice.

 2013.02.05

SLE-73_INSSXEN_v.2.05.000 

Summary of Contents for SLE-73

Page 1: ...OUNTER SLE 73 Firmware v 4 00 or higher Input type pulse Low cost counter Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes...

Page 2: ...7 3 5 rS 485 menu 18 7 3 6 SEtcod parameter 20 7 3 7 briGHt parameter 20 7 3 8 Edit parameter 20 7 3 9 dEFS parameter 20 7 4 MENU STRUCTURE 21 8 EXAMPLES OF PRESCALER PARAMETERS CALCULATION 22 9 THE...

Page 3: ...ation of troubleshooting in the case of malfunction Neighbouring and connected equipment must meet the appropriate standards and regulations concerning safety and be equipped with adequate overvoltage...

Page 4: ...any time but needs confirmation by ENTER button Using local keyboard user can change all parameters as wish and access to settings menu can be protected by 4 digit user defined password Thanks to sma...

Page 5: ...ding to PN EN 61326 1 This is a class A unit In housing or a similar area it can cause radio frequency interference In such cases the user can be requested to use appropriate preventive measures 4 DEV...

Page 6: ...es with the governing regulations Disconnect the power supply prior to starting assembly Check the connections are wired correctly prior to switching the unit on In order to install the unit a 66 5 x...

Page 7: ...nual COUNTER SLE 73 b Figure 4 1 Mounting hole dimensions a recommended b allowable Figure 4 2 Installing of brackets and dimensions of connectors 7 68 mm max 5 mm 32 5 mm 92 mm 5 mm 12 mm 10 mm 8 5 m...

Page 8: ...must be selected in such a way that in the case of a short circuit of the cable from the side of the unit the cable shall be protected against destruction with an electrical installation fuse Wiring...

Page 9: ...duction loads should be equipped with anti interference protection systems e g RC type Use of screened signal cables is recommended Signal cable screens should be connected to the earthing only at one...

Page 10: ...e made while power supply is disconnected Depending on version 85 230 260V AC DC or 19 24 50V DC 16 24 35V AC Figure 4 6 Connection of power supply 10 1 2 10 6 7 8 9 18 19 20 17 16 GND DATA DATA RS 48...

Page 11: ...ely high temperatures cause faster ageing of the internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning use wa...

Page 12: ...ons zeroing the counter see rESEt option page 17 the reset must be confirmed by ENTER button 6 PRINCIPLE OF OPERATION After turning the power supply on device ID and software version are showed on the...

Page 13: ...ble the connection of the simple switches as detectors special digital filter has been build into the device This filter allows the counter to proper counting pulses regardless of the vibration of the...

Page 14: ...agraph MENU DESCRIPTION 7 1 PROGRAMMING MENU To enter main menu being in the measurement mode operator must to press and hold at least 2 sec ESC MENU button If the user password is defined see paramet...

Page 15: ...1 Numeric parameters digit change mode Numerical parameters are displayed as decimal numbers The mode of its new value entering depends on chosen edit method see parameter Edit In mode by digit Edit d...

Page 16: ...hanges are accepted stored in EEPROM end the edition process finished Pressing the key ESC after SEt causes in cancelling of made changes and returning to menu Functions of buttons when editing numeri...

Page 17: ...is disabled nonE this option disables both manual and electronic reset Zeroing of the counter can be done via RS 485 interface by presets of some registers with value 0000h independently of the rESEt...

Page 18: ...ter modulo and main counter are internal registers of the counter s firmware and they contain not calculated by mul and div parameters numbers of pulses delivered to the counting inputs A and B The mo...

Page 19: ...l additional delay between the Modbus message and the answer of the device received and sent via RS 485 interface This additional delay allows the device to work with poor RS converters which do not w...

Page 20: ...ord can be used ONE TIME ONLY it is impossible to use it again The one use password can be restored by Service Division only 7 3 7 briGHt parameter This parameter allows user to set bright of the LED...

Page 21: ...int Parameter edition FiLtEr MENU ESC MENU ESC PrESCA ENTER MENU ESC ENTER Parameter edition Parameter edition MENU ESC rS 485 MENU ESC Edit ENTER MENU ESC MENU ESC dEFS ENTER MENU ESC Parameter editi...

Page 22: ...bits 1 or 2 stop bit 2 bits are send 1 and 2 bits are accepted when receive no parity control Baud rate selectable from 1200 to 115200 bits second Transmission protocol MODBUS RTU compatible The devic...

Page 23: ...S 485 interface 3 mode nonE reset with RS 485 interface only 14h Yes 0 9 FiLtEr option filtering rate 0 for input signal up to 3kHz frequency 1 up to 10Hz 2 up to 20Hz 3 up to 30Hz 4 up to 40Hz 5 up t...

Page 24: ...ing to register no 20h the device responds with an old address in the message 4 after writing to register no 22h the device responds with the new baud rate 5 the value of the mbAccE parameter is also...

Page 25: ...ror check Hi and Lo byte 1 Read of device ID code ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 21 00 01 D4 00 The answer ADDR FUNC BYTE C DATA H L CRC L H 01 03 02 20 CC A1 D1 DATA identification code...

Page 26: ...of displayed value 00 5 Read of the displayed value high and low word ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 01 00 02 95 CB Response while normal operation no errors ADDR FUNC BYTE C DATA H1 L1...

Page 27: ...H L DATA H L CRC L H 01 06 00 22 00 09 E9 C6 DATA L 9 value exceeds allowable range 0 7 The answer exception code 03h illegal data value ADDR FUNC ERR CRC L H 01 86 03 02 61 There is no full implemen...

Page 28: ...plier 1 18 div divider 1 18 oFFSEt Offset constant value added to the result to move the zero point of the current scale 0 18 Point Decimal point position 0 0 18 RS 485 interface configuration rS 485...

Page 29: ...User manual COUNTER SLE 73 29...

Page 30: ...User manual COUNTER SLE 73 30...

Page 31: ...User manual COUNTER SLE 73 31...

Page 32: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...