6
1.1 INTRODUCTION
The
“PLANET SUPER 4 W.M.”
wall hung
boilers with D.H.W. storage tank allow a
variety of requests to be met thanks to the
abundance of water which the capacious
tank unit (with optional secondary circula-
tion, see fig. xx) makes available and thanks
also to an electronic management and con-
trol system via a microprocessor.
They are designed and built in compliance
with European directives 90/396/EEC,
89/336/EEC, 73/23/EEC, 92/42/EEC
and the European norms EN 483 - EN 625.
They may be fuelled by natural gas (metha-
ne) and butane gas (G30) or propane
(G31).
Follow the instructions given in this manual
for the correct installation and perfect
functioning of the apparatus.
1
DESCRIPTION OF THE BOILER
1.2
DIMENSIONS
100 152 70100 78
E U M R G
156
90
865
600
ø 60/1
00
222
450
460
=
=
93
4
29
7
22
850
5
Fig. 1
CONNECTIONS
A C.H. return
3/4”
B C.H. flow
3/4”
C Gas connection 1/2” BSP
D D.H.W. inlet
1/2”
E
D.H.W. outlet
1/2”
1.3
TECHNICAL FEATURES
*
Flow calculated with a fixed temperature on the D.H.W. potentiometer of 60 °C for a maximum period of 10 minutes.
**
The gas flow refers to the inferior calorific value in standard conditions of 15°C - 1013 mbar
*** Differential measure between the pressure upstream of the gas valve and the depression in sealed chamber.
SUPER 4 W.M.
Heat output
Nominal
kW
11,6÷29,5
Btu/h
39.600÷100.650
Nominal
kW (Btu/h)
29,5 (100.650)
Heat input
Nominal
kW
13,5÷31,6
Btu/h
46.050÷107.800
Minimum
kW (Btu/h)
13,5 (46.050)
Class NOx
3
Losses after shutdown to 50°C
W/h
118
Water content
l
5
Expansion vessel
Capacity
l 8
Preloading pressure
bar
1
C.H. setting range
°C
40÷80
D.H.W. setting range
°C
10÷60
D.H.W. production
Tank unit capacity
l
60
D.H.W. flow rate EN 625*
l/min
15,7
Contin. D.H.W. flow rate (
∆
t 30°C)
l/h
845
D.H.W. expansion vessel
l
2,5
Tank unit maximum water head
bar
7
Recovery time from 25 to 55°C
min
4’30”
Absorbed power consumption
W
180
SUPER 4 W.M.
Electrical protection grade
IP X4D
Maximum water head
bar
3
Maximum temperature
°C
85
Smokes temperature
°C
123
Smokes flow
gr/s
20,0
Category
II2H3+
Type
C12-32-42-52
Shipping weight
kg
99
Main gas nozzles
Quantity
n°
15
Natural gas
ø mm
1,30
G30 - G31
ø mm
0,76
Gas flow **
Natural gas
m
3
/h
3,34
Butane (G30)
kg/h
2,44
Propane (G31) LPG
kg/h
2,40
Burner gas pressure ***
Natural gas
mbar
2,2÷11,3
Butane (G30)
mbar
5,5÷28,0
Propane (G31) LPG
mbar
5,5÷36,0
Gas supply pressure
Natural gas
mbar
20
Butane (G30)
mbar
28 - 30
Propane (G31) LPG
mbar
37
D
B
E
A
C