i n s t a l l e d a n d s h o u l d n o t e xc e e d 16
mmH
2
O.
When t he lengt h of t he f lues r anges
between 11 and 16 mm H
2
0, it is neces-
sary to adjust trimmer “MAX” on the fan
board and set the “Max. air
Δ
p” values pro-
vided in paragraph 4.3 in order to ensure a
correct operation.
2.6.4
Maximum usable
length for coaxial
ø 80/125 flues
In installations with ø 80/125 coaxial
exhaust, the maximum horizontal length
including t he 90° cur ve, should no t
exceed 5 m. For roof exits it should not
exceed 8 m along vertical linear sections.
When the length of the flue ranges from 2
to 5 m horizontally and from 4 to 8 m verti-
cally, it is necessary to adjust trimmer
“MAX” on the fan board and set the “Max.
air
Δ
p” values provided in paragraph 4.3 in
order to ensure a correct operation.
WARNING:
- Installations with roof exit terminal (4a) and coaxial exhaust (13) require the use of a condensation recovery (12)
that has to be connected to the water drain siphon (waste water).
- The installation of the roof exit terminal (4a) requires the removal of the two ø 60 and ø 100 reducers.
- Before fitting the accessories, it is always advisable to lubricate the internal section of the gaskets with silicon
products and generally avoid the use of oils and greases.
TABLE OF LOAD LOSSES OF ACCESSORIES
Fig. 4/a
KEY
1
ø 80 polypropylene curve, 90° MF (6 pcs) code 8077450
2 a ø 80 polypropylene extension, L. 1000 (6 pcs.) code 8077351
2 b ø 80 polypropylene extension, L. 500 (6 pcs.) code 8077350
3
Hinged tile, code 8091300
4
Roof exit terminal, L. 1381, code 8091204
4 a Coaxial roof exit terminal, L. 1285 code 8091205
5
ø 80 polypropylene extension, L. 250, with socket, code 6296513
6
ø 80polypropylene curve, 45° MF (6 pcs.), code 8077451
7
ø 80 exhaust terminal, code 8089501
8
Kit with internal/external ring nuts, code 8091500
9
ø 80 suction terminal (supplied with unit)
10
Suction/exhaust fitting, code 8091401
11
ø 80 rubber gasket (supplied with unit)
12
ø 80 condensation recovery, L. 135, code 8092800
13
ø 80/125 coaxial exhaust, L. 885, code 8091210
Load loss (mm H
2
O)
Suction Exhaust
90° MF polypropylene curve
1,00
1,30
45° MF polypropylene curve
0,60
0,70
Polypropylene extension, L.1000
0,60
0,60
Polypropylene extension L.500
0,30
0,30
Coaxial roof exit terminal, L.1285 + Fitting (pos. 10)
-
4,30
Roof exit terminal L.1381
-
1,20
Exhaust terminal
-
1,30
Suction terminal
0,20
-
Polypropylene extension, L. 250 with socket
-
0,15
Coaxial exhaust, L.885 + Fitting (pos. 10)
-
5,20
Condensation recovery, L.135
2,50
-
Type C (separate ø 80 flues and
coaxial exhaust terminal)
Type C (separate ø 80 flues)
Summary of Contents for Planet Dewy 60 BFR
Page 1: ...Planet Dewy 60 BFR IT CERTIFICAZIONE DEL SISTEMA DI QUALITA AZIENDALE ES FR BE GB RUS RO...
Page 128: ...126 RO RUS GB BE FR ES IT...
Page 153: ...1 152 2 154 3 161 4 164 SIM 27 90 396 CEE 110 C PED 97 23 CEE 1 3 6 PLANET DEWY 60 BFR...
Page 170: ...168 IT ES FR BE GB RUS RO 1 1 FF 2 35 80 C 55 C APRE SPIA VERDE SPIA GIALLA SPIA ROSSA 1 2...
Page 173: ...171 IT ES FR BE GB RUS RO 1 1 Info Info...
Page 174: ...172 IT ES FR BE GB RUS RO 5 61 1 2 3 61 1 3 4 11 12 14 15 17 18 19...
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......