41
3.5.6 DHW
PARAMETERS MENU
GENERAL SETTINGS
GENERATION
I/O CONFIGURATION
HEATING
COOLING
DOMESTIC HOT WATER
ENERGY SETTINGS
Press
to access domestic hot water.
Comfort Setpoint Temperature for DHW
DOMESTIC HOT WATER
S600
COMFORT
SETPOINT TEMPERATURE
FOR DHW:
55.0ºc
PAR.
DESCRIPTION
RANGE
6000
COMFORT Setpoint Temperature for DHW
[°C]
·
10.0 - 80.0
The DHW COMFORT temperature can be set manually (it is the
same value which can be modified in the user menu).
Reduced Setpoint Temperature for DHW
DOMESTIC HOT WATER
S602
REDUCED
SETPOINT TEMPERATURE
FOR DHW:
45.0ºc
PAR.
DESCRIPTION
RANGE
6010
REDUCED Setpoint Temperature for DHW
[°C]
·
10.0 - 80.0
The DHW REDUCED temperature can be set manually (it is
the same value which can be modified in the user menu).
Maintaining Storage Tank When In Reduced Mode
DOMESTIC HOT WATER
S606
MAINTAINING STORAGE
TANK IN REDUCED MODE:
DISABLED
PAR.
DESCRIPTION
RANGE
6060
Maintaining Storage Tank When In Re-
duced Mode
·
Disabled
·
Enabled
When in DHW REDUCED mode, it is possible to enable/disable
the heat pump from maintaining the storage tank at the calcu-
lated setpoint temperature.
DHW Anti-legionella Function
DOMESTIC HOT WATER
S611
ANTI-LEGIONELLA
FUNCTION
Activation : NOT ACTIVE
Day :
MONDAY
Start Time : 00:00
End Time
: 03:00
Setpoint :
55.0ºc
PAR.
DESCRIPTION
RANGE
6120
DHW Anti-Legionella Function
Enabled
·
OFF
·
ON
6122
Anti-Legionella Function Start Day
·
1 - Mon ÷ 7 – Sun
6123
Anti-Legionella Function Start Time
·
00 - 23
6125
Anti-Legionella Function Stop Time
·
00 - 23
6127
Anti-Legionella DHW Temperature
Setpoint
·
10.0 - 80.0
Settings relating to the anti-legionella function: Activation,
Day of the week, Start time, End time, Setpoint.
This function requires the Heat Pump to prepare the storage
tank on the basis of the parameters set here but only if in the
previous 7 days, the temperature has not reached the anti-le-
gionella setpoint value.
DHW Storage Tank Dynamic Setpoint
DOMESTIC HOT WATER
S615
DHW STORAGE TANK
DYNAMIC SETPOINT:
ENABLED
PAR.
DESCRIPTION
RANGE
6150
DHW Storage Tank Dynamic Setpoint
·
Disabled
·
Enabled
If the DHW STORAGE TANK DYNAMIC SETPOINT , is activated,
it allows the DHW storage tank to be maintained by the Heat
Pump up to the heat pump convenience temperature (not ex-
ceeding the DHW setpoint) rather than the fixed nominal set-
point.
Summary of Contents for Open Hybrid MEM 25-006