29
7 commissioning
7.1
preliminary operations
Before commissioning the appliance, check that:
– the type of gas is correct for the appliance
– the gas isolation valves for the heating system and the water
system are open
– the system pressure as shown on the pressure gauge when
the system is cold , is between 1 and 1.2 bar
– the pump impeller rotates freely.
7.2
before commissioning
after having carried out the preliminary operations, proceed
as follows:
– set the main system switch to "oN"
– the type of gas for which the boiler has been calibrated, “ng”
(methane) or “lg” (lPG,) will appear followed by the power.
Finally “- -”will appear on the display
– press the button
s
once for at least 1 second to select
"sUMMeR mode"
l
. the value of the delivery sensor
detected at that moment will appear on the display
– open one or more than one hot water tap. the
r
should
appear on the display and the boiler will ignite and stay
alight until the tap is turned off.
– if there is a fault, the message “al” will appear on the display
followed by the fault code (eg. “06” - no flame detected).
m
caUtion
if the boiler has blocked, restore the start conditions
by pressing and holding the button
o
(
R
) for more
than 3 seconds. this operation can be carried out no
more than 6 times.
– close the taps opened previously and check that the
appliance shuts down
– press the button
s
once to select "WiNteR mode"
n
. the
value of the heating water temperature detected at that
moment will appear on the display
– operate the heating controls and check that the boiler starts
and operates correctly
– to check that the pressure in the network and the nozzles
are correct, the procedure described in section must be
carried out "chimney sweep function".
– record in Benchmark commissioning Check list (page 39).
7.3
parameter setting and display
to go into the parameter menu:
– from the selected mode (eg. WiNteR)
– press the buttons
<
and
o
(approximately 5 seconds) at the
same time until “ts” (installer) appears on the 2 digits of the
display which alternate with “0.1” (parameter number) and
a “1” (set value)
– press the button
>
to scroll up the list of parameters and
then
<
to scroll down the list
note:
holding the buttons
>
or
<
increases the speed of the
scrolling movement.
– once the required parameter has been reached, press
the button
o
for approximately 3 seconds to confirm and
access the set value which will then flash and can then be
modified
– to modify the value in the permitted range, press the buttons
>
to increase it or
<
to decrease it
– once the required value has been reached, press the button
o
to confirm.