NOTE: the inside of the upper door of
the boiler panel has a label with the
values that have to be set for PAR 1 and
PAR 2 (fig. 19).
3.3.2 Warning
Should.the.boiler.operation.not.be.opti-
mal. but. no. alarm. sets. off,. press. the.
button..
5
3
1
2
4
.until.info.70.and.the.warning.
code.associated.to.the.ongoing.event.are.
displayed.. Once. optimal. operation. is.
restored,.info.70.will.display:.“-.-”.
Below.is.the.table.of.warning.codes:.
PARAMETERS INSTALLER
EXPANSION CARD
PAR.DESCRIPTION...
RANGE.
UNIT.OF.
INC/DEC.. DEFAULT
.
.
.
MEASUREMENT. UNIT.
SETTING
40. Number.of.expansion.boards..
0.....3.
=.
1.
0
41. Mix.valve.stroke.time.
0.....199.
10.sec..
1.
12
42. Priority.of.D.H.W..over.mixed.zone.
0.=.Paralle.
=.
=.
1
.
.
1.=.Absolute
43. Floor.drying.
0.=.No.activated.
=.
=.
0
.
.
1.=.Curve.A
.
.
2.=.Curve.B
.
.
3.=.Curve.A+B
44. Type.of.solar.system.
1.....8.
=.
1.
1
45.
∆
t.solar.collector.pump.1.
PAR.74.OEM.-.1....50.
°C.
1.
8
46. Solar.integration.delay..
“--”,.0.....199.
Min..
1.
0
47. Tmin.solar.collector.
“--”,.-30.....0.
°C.
1.
-.10
48. Tmax.solar.collector.
“--”,.80.....199.
°C.
1.
120
PARAMETERS RESTORATION
PAR.DESCRIPTION...
RANGE.
UNIT.OF.
INC/DEC.. DEFAULT
.
.
.
MEASUREMENT. UNIT.
SETTING
49.*. Reset.default.parameters.
--.,.1.
=.
=.
=
.
(par.01.-.par.02.=..“-“)
* In case of difficulty in understanding the current setting or in case of an anomalous or
incomprehensible conduct of the boiler, we suggest to restore the initial values of the parameters
setting PAR 49 = 1 and the PAR 1 and PAR 2 as specified at point 3.3.1.
CASCADE CONNECTION PARAMETERS
When the appliance is installed in sequence/cascade (modular system
with several generators) it is necessary to set the following INST
parameter on all connected burners:
PAR 15 =
0 for the first boiler (MASTER)
1 .... 7 for the other boilers (SLAVE)
(Avoid assigning the same number to SLAVE boilers)
Set the following INST parameter if polypropylene smoke collectors
with a clapet valve are used in sequence/cascade installations:
PAR 1 =
61 (for NATURAL GAS boilers)
63 (for PROPANE boilers)
In addition, when the number of boilers in cascade is more than two,
configure the parameters OEM A1 of the MASTER boiler.
To access the OEM parameters press simultaneously the buttons (
5
3
1
2
4
and
5
3
1
2
4
) for 2 seconds. Entered in the INST level again press simulta-
neously he buttons (
5
3
1
2
4
and
5
3
1
2
4
) for another 2 seconds.
At this point insert the access code formed by this sequence of
INSTALLATOR BUTTONS:
“ + / - / < / > / < “.
Set the parameter:
PAR A1 =
Number of cascade generators (3 ... 8)
CODE
DESCRIPTION
. E0.
Reduced.capacity.operation.
.
.
(∆t.between.delivery.and.return.
.
.
over.40°C)
. E1.
Shorted.external.sensor.(SE)
E2.
Preheating.function.active
. E3.
TBD
. E4.
TBD
. E5.
TBD
. E6.
TBD
. E7.
TBD
. E8.
TBD
. E9.
TBD
BOILER
PAR 2
.
Instant.with.deviator.valve..
1
.
and.flowmeter
.
. Instant.with.deviator.valve,..
2
.flowmeter.and.solar.combination
.
D.H.W..tank.with.
.deviator.valve.and.boiler.sensor..
3
.
vers..T.(LOW.INERTIA)
.
. On.board.D.H.W..tank.with
.deviator.valve.and.D.H.W..sensor...
4
.
(LOW.INERTIA)
.
.Remote.D.H.W..tank.with.deviator.
. valve.and.D.H.W..thermostat...
5
.
or.heating.only.vers..T/R.boiler
.
(LOW.INERTIA)
. On.board.D.H.W..tank.with
.double.pump.and.D.H.W..sensor...
6
.
vers..T/R.boiler.
.
(LOW.INERTIA)
. On.board.D.H.W..tank.with
.
double.pump.and.D.H.W..
. thermostat.vers..T/R.boiler...
8
.
(LOW.INERTIA)
.
.
Heating.only.with
.
antifreeze.sensor...
9
.
(LOW.INERTIA)