Type C (ø 80/125 coaxial exhaust)
NOTES:
- Installation requires the use of a condensation
recovery (12) that must be connected to a
water drain siphon (waste water).
- The installation of the coaxial roof exit terminal
(4a) requires the removal of the two ø 60 and ø
100 reducers.
- Before installing accessories, lubricate the
internal part of gaskets with silicon-based pro-
ducts. Avoid using oils and greases.
- Inserting each supplementary 90° elbow redu-
ces the available segment by 1 metres and
Inserting each supplementary 45° elbow redu-
ces the available segment by 0.5 metre.
KEY
2 a
Extension ø 80/125 L. 1000 code 8096171
2 b
Extension ø 80/125 L. 500 code 8096170
3
Hinged tile code 8091300
4 a
Coaxial roof exit terminal code 8091205
10
Inlet/exhaust fitting with test outlet code 8091401
11
Rubber gasket ø 80 (supplied as standard)
12
Condensation recovery ø 80 L. 135 code 8092800
13
Coaxial exhaust ø 80/125 L. 885 code 8091210
14 a 90° curve ø 80/125 code 8095870
14 b 45° curve ø 80/125 code 8095970
Fig. 8
Model
Gas connection
H (m)
L (m)
110 R
G20
5
4
110 R
G31
4
3
VERTICAL EXHAUST
To ensure correct operation of the appliance, do as
follows:
- set the installer parameter PAR 9 as indicated in
TABLE 3 (see point 3.3 to access the installer
parameters).
- proceed with calibrating CO
2
at the maximum and
minimum capacity as specified in point 4.2.2.
TABLE 3
Maximum length
PAR 9
exhaust (m)
(long chimneys)
0 - 1,0
6
1,0 - 2,0
7
2,0 - 3,0
8
3,0 - 4,0
9
4,0 - 5,0
10
HORIZONTAL EXHAUST
To ensure correct operation of the appliance, do as
follows:
- set the installer parameter PAR 9 as indicated in
TABLE 3/a (see point 3.3 to access the installer
parameters).
- proceed with calibrating CO
2
at the maximum and
minimum capacity as specified in point 4.2.2.
TABLE 3/a
Maximum length
PAR 9
exhaust (m)
(long chimneys)
0 - 1,0
7
1,0 - 2,0
8
2,0 - 3,0
9
3,0 - 4,0
10