MURELLE HE 110 R
Heat output
Nominal (80-60°C)
kW
105.6
Nominal (50-30°C)
kW
114.6
Reduced (80-60°C)
kW
21.1
Reduced (50-30°C)
kW
23.6
Heat input nominal
kW
108
Heat input reduced
kW
21.6
Max/min useful yield (80-60°C)
%
97.7/97.8
Max/min useful yield (50-30°C)
%
109.1/106.1
Useful yield at 30% of the load (40-30°C)
%
105.6
Termal efficiency (CEE 92/42 directive)
Losses after shutdown to 50°C (EN 483)
W
126
Supply voltage
V-Hz
230-50
Adsorbed power consumption
W
309
Electrical protection grade
IP
X4D
C.H. setting range
°C
20/80
Water content boiler
l
8.2
Maximum water head
bar
5
Maximum temperature
°C
85
Capacity of the heating expansion vessel
l
--
Pressure of the heating expansion vessel
bar
--
D.H.W. setting range
°C
--
D.H.W. flow rate (EN 625)
l/min
--
Continuous D.H.W. flow rate
∆
t 30°C
l/min
--
Minimum D.H.W. flow rate
l/min
--
D.H.W. pressure min/max
bar
--
D.H.W. pressure min. nom. power
bar
--
Exhaust fumes temperature at max flow rate (80-60°C)
°C
86.2
Exhaust fumes temperature at min. flow rate (80-60°C)
°C
74.6
Exhaust fumes temperature at max flow rate (50-30°C)
°C
61.6
Exhaust fumes temperature at min. flow rate (50-30°C)
°C
49.2
Smokes flow min/max
kg/h
37/186
CO
2
at max/min flow rate G20
%
9.0/9.0
CO
2
at max/min flow rate G31
%
10.2/10.2
CE certification
n°
1312CM5614
Category
II2H3P
Type
B23-53/B23P-53P/C13-33-43-53-83
NOx emission class
5 (< 30 mg/kWh)
Weight when empty
kg
87
Main burner nozzle
Quantity nozzles
n°
1
G20 nozzle diameter
ø
12.4
G31 nozzle diameter
ø
8.2
Consumption at maximum/minimum flow rate
Maximum G20
m
3
/h
11.42
Minimum G20
m
3
/h
2.28
Maximum G31
kg/h
8.38
Minimum G31
kg/h
1.68
Gas supply pressure
G20
mbar
20
G31
mbar
37
1.3
TECHNICAL FEATURES