1.6
Fault / malfunction codes
If a fault/malfunction is detected during boiler operation, the
message
"E"
will appear on the display followed by the fault
code.
If you see alarm
“04”
(low water pressure in the system):
– using a pressure gauge (1), check that the heating system
pressure when cold is
1-1.2 bar
. If this is not the case, open
the filling valve (2) and restore the heating system pressure
until the pressure gauge (1) shows a reading of
1-1.2 bar
– close the filling valve (2)
– turn dial
t
to
6
/
R
and then again to the adjustment value
required. This resets normal operating conditions.
2
1
Fig. 8
If you see alarm
“E01”
(no flame detected):
– turn dial
t
to
6
/
R
and then again to the adjustment value
required. This resets normal operating conditions.
OFF
RESET
Fig. 9
If this operation is not successful,
ONLY ONE MORE RESET
ATTEMPT
can be made, therefore:
– close the gas isolation valve
– set the main system switch to "OFF"
– contact the Qualified Technical Personnel.
OFF
Fig. 10
m
CAUTION
Should you see an alarm not described here, contact a
qualified technical professional
.
2 SHUTDOWN
2.1
Temporary shutdown
If the boiler is to be left unused for a long period, the following
operations need to be carried out::
– turn dial
t
to
6
/
R
. The display will show
"- -"
. If an
external sensor is connected, the display will show icon
3
and the value of the external temperature detected.
OFF
RESET
Fig. 11
f
ELECTRICAL HAZARD
The boiler will still be powered.
If the user is away temporarily (for a weekend, short trip etc)
and if the outside temperature is at ZERO:
– turn dial
t
to
6
/
R
– set the main system switch to "OFF"
– close the gas valve.
OFF
RESET
OFF
Fig. 12
m
CAUTION
If the outside temperature might fall below ZERO,
since the appliance is equipped with an "antifreeze
function"
– turn dial
t
to
6
/
R
– leave the main system switch set to "ON" (boiler is
powered)
– leave the gas valve open.
ON
Fig. 13
Summary of Contents for GO 18 BF G20
Page 10: ...10 ES...
Page 18: ...18 ES...
Page 41: ...41 ES...
Page 50: ...50 EN...
Page 58: ...58 EN...
Page 81: ...81 EN...
Page 83: ...83 RU m Sime 1 1 2 OFF Sime X m Fonderie SIME S p A...
Page 84: ...84 RU d 8 8 OFF d EN 15502 60 C 5 C...
Page 90: ...90 RU...
Page 91: ...91 RU 5 92 5 1 92 5 2 92 5 3 92 5 4 93 5 5 94 5 6 95 5 7 95 5 8 95 5 9 96 5 10 96 5 11 97...
Page 98: ...98 RU...
Page 101: ...101 RU 50 mm 300 mm 900 mm 25 6 5 GO BF m 6 6 m Y R 6 7 pH 6 8 25 f 6 8 GO BF 1 2 3 1 2 3 26...
Page 109: ...109 RU 6 13 2 3 4 7 7 3 4 3 7 45...
Page 111: ...111 RU 7 3 m 1 2 1 2 49 t 6 OFF RESET 50 5 tS0 1 1 1 1 1 1 1 5 5...
Page 116: ...116 RU 7 8 Auto MAnu 1 5 m 6 7 65 tS 1 7 5 t D 5 Auto OFF RESET 66 P01 0 150 6 D 67...
Page 118: ...118 RU 8 8 1 m a OFF OFF 70 8 2 8 2 1 d 8 3 8 3 1 1 2 1 2 71 3 4 4 5 6 3 72 5 6 5...
Page 119: ...119 RU 8 3 2 8 3 3 3 5mm 0 5 0 5 73 m 8 3 4 4 4 4 74 8 4 8 4 1 8 4 2 1 8 5...
Page 121: ...121 RU...
Page 122: ...122...
Page 123: ...123...