The maximum overall length of the
intake and exhaust ducts depends on
the head losses of the single fittings
installed and must not be greater than
7.6 mm H
2
O vers. “25 Solar” - 9 mm H
2
O
vers. “30 Solar”.
For head losses in the fittings, refer to
Table
1 and example fig. 8/a
.
2.9.1
Separate flue kit
(fig. 9)
The separate flue kit code 8089904 is
supplied with an intake diaphragm which
must be used as shown in fig. 9/a, depen-
ding on the maximum load loss permitted
in both flues. To use the air intake in this
type of outlet you must perform the fol-
lowing operations (fig. 10):
–Remove the base of the air intake, using
a tool to cut it off (a);
79
IT
ES
PT
GB
Example of allowable installation
“25 Solar”
calculation in that the sum of the head losses of
the single fittings is less than 7.6 mm H
2
O:
Intake
Outlet
7 meter horizontal pipe ø 80 x 0.20
1.40
–
7 meter vertical pipe ø 80 x 0.30
–2.10
n° 2 90° elbows ø 80 x 0.30
0.60
–
n° 2 90° elbows ø 80 x 0.40
–0.80
n° 1 terminal ø 80
0.10
0.30
Total head loss
2.10
+
3.20 =
5
.
3 mm H
2
O
With this total head loss, remove the segments from n. 1 to n. 7 from diaphragm in the
intake pipe.
165
110
165
K
ø 80
ø 80
100
92
1
2
3
4
6
Fig. 9
Fig. 9/a
Fig. 8/a
KEY
1
ø125/95 sponge seal
2
Fixing screw
3
Flue outlet flange
4
Inlet air diaphragm
6
Manifold with intakes
“30 Solar”
25
30
K mm
180
205
H mm
125
165
N° segments
Total load loss mm H
2
O
to remove
25 Solar
30 Solar
none
0 ÷ 0.8
-
n° 1
0.8 ÷ 1.6
-
n° 1 e 2
1.6 ÷ 2.4
0 ÷ 1.0
da n° 1 a 3
2.4 ÷ 3.1
1.0 ÷ 2.0
da n° 1 a 4
3.1 ÷ 3.8
2.0 ÷ 3.0
da n° 1 a 5
3.8 ÷ 4.5
3.0 ÷ 4.0
da n° 1 a 6
4.5 ÷ 5.2
4.0 ÷ 4.8
da n° 1 a 7
5.2 ÷ 5.8
4.8 ÷ 5.6
da n° 1 a 8
5.8 ÷ 6.4
5.6 ÷ 6.4
da n° 1 a 9
6.4 ÷ 7.0
6.4 ÷ 7.2
da n° 1 a 10
-
7.2 ÷ 8.0
without diaphragm
7.0 ÷ 7.6
8.0 ÷ 9.0
H
TABLE 1
Accessories ø 80
Load loss (mm H2O)
“25 Solar”
“30 Solar”
Intake
Outlet
Roof out. Intake
Release
Outlet
Roof out. Intake
90° curve MF
0.30
0.40
–0.30
0.45
–
45° curve MF
0.20
0.30
–0.20
0.35
–
Extension L. 1000 (horizontal)
0.20
0.30
–0.20
0.35
–
Extension L. 1000 (vertical)
0.30
0.20
–0.30
0.25
–
Outlet terminal
–0.30
– –0.35
–
Intake terminal
0.10
––
0.10
––
Manifold
0.20
––
0.30
––
Roof outlet terminal L.1390
––
0,50
––
0.55
Condensation collection T
–1.00
– –1.05
–