32
9.3
Parameter setting and display
To go into the parameter menu:
– from the selected mode (eg. WINTER)
– press the buttons
(
and
t
(for approximately 5 seconds)
at the same time until
“PAR 01”
(parameter number) and the
value set (0-4) appears on the display
– press the button
t
to scroll up the list of parameters and
then
(
to scroll down the list
NOTE:
holding the buttons
(
or
t
increases the speed of the
scrolling movement.
– once the required parameter has been reached, press the
buttons
>
or
<
to modify the value within the permitted range.
The modifications are stored automatically.
When all the parameter modifications have been made, exit the
parameter menu by pressing and holding down the buttons
(
and
t
at the same time
until the initial screen is displayed.
NOTE:
In case of power failure all settings are stored.
9.4
List of parameters
Type
No.
Description
Range
U/M
Step
Default
CONFIGURATION
PAR
01
Index showing boiler power in kW
1 = 25; 2 = 30; 3 = 35; 4 = 40
1 .. 4
-
1
1 or 4
PAR
02
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
5 = open vent
6 = boiler with heat pump
0 .. 6
-
1
1
PAR
03
Gas Type Configuration
0 = NATURAL GAS; 1 = UNIVERSAL LPG
0 .. 1
-
1
0
PAR
04
Combustion configuration
0 = sealed chamber with combustion control
-
-
-
0
PAR
08
External sensor value correction
-5 .. +5
°C
1
0
PAR
09
Ignition fan speed
80 .. 160
RPMx25
1
128
DOMESTIC HOT WATER - HEATING
PAR
10
Boiler Antifreeze Threshold
0 .. +10
°C
1
3
PAR
11
External Sensor Antifreeze Threshold
-- = Disabled
-9 .. +5
°C
1
-2
PAR
12
Heating Curve Incline
0 .. 80
-
1
20
PAR
13
Minimum Heating Temperature Adjustment
20 .. PAR 14
°C
1
20
PAR
14
Maximum Heating Temperature Adjustment
PAR 13 .. 80
°C
1
80
PAR
15
Maximum power heating
0 .. 100
%
1
100
PAR
16
Heating Post-Circulation Time
0 .. 99
seconds
x 10
1
3
PAR
17
Heating Pump Activation Delay
0 .. 60
seconds
x 10
1
0
PAR
18
Re-ignition Delay
0 .. 60
Min
1
3
PAR
21
Minimum power heating/domestic hot water (premixed)
0 .. 100
%
1
0
PAR
23
External relay 1 function
0 = not used; 1 = remote alarm NO; 2 = remote alarm NC; 3 = zone
valve; 4 = automatic filling; 5 = external request; 6 = recirculation
pump; 7 = zone valve with OT; 8 = relaunch pump; 9 = boiler with heat
pump (circulator)
0 .. 9
-
-
0
Summary of Contents for Brava Slim HE 20 R i
Page 4: ...4 ...
Page 42: ...42 12 EXPLODED VIEWS Brava Slim HE 20 R i Brava Slim HE 40 R i ...
Page 43: ...43 Brava Slim HE 20 R e Brava Slim HE 40 R e ...
Page 44: ...44 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Page 45: ...45 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Page 46: ...46 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Page 55: ...55 ...