86
EN
Type
No. Description
Range
U/M
Step
Default
DOMESTIC HOT WATER - HEATING
PAR
20 Minimum Tset Zone 1 Heating
Par 64 OEM .. Par 21
°C
1
20
PAR
21 Maximum Tset Zone 1 Heating
Par 20 .. Par 65 OEM
°C
1
80
PAR
22 Heating Curve Grade Zone 1 3...40
3...40
-
1
20
PAR
23 Minimum Tset Zone 2 Heating
Par 64 OEM .. Par 24
°C
1
20
PAR
24 Maximum Tset Zone 2 Heating
Par 23 .. Par 65 OEM
°C
1
80
PAR
25 Heating Curve Grade Zone 2 3...40
3...40
-
1
20
PAR
26 Minimum Tset Zone 3 Heating
Par 64 OEM ..
.. Par 27
°C
1
20
PAR
27 Maximum Tset Zone 3 Heating
Par 26 .. Par 65 OEM
°C
1
80
PAR
28 Heating Curve Grade Zone 3 3...40
3...40
-
1
20
PAR
29 ∆T heating
10…40
°C
1
20
PAR
30 Heating Post-Circulation Time
0 .. 199
Sec
10
30
PAR
31 Heating Maximum Output
30 ..100
%
1
100
PAR
32 Pump Activation Delay Zone 1
0 .. 199
10 Sec
1
1
PAR
33 Re-ignition Delay
0 ..10
Min
1
3
PAR
34 Supplementary sources activation threshold
--,
-10…40
°C
1
-
PAR
35 Boiler Antifreeze Threshold
0…+20
°C
1
3
PAR
36 External Sensor Antifreeze Threshold
-5…+5
°C
1
-2
PAR
37 Flow meter Modulation Saturation Band
-- = Disabled 0….100
%
1
100
PAR
38 DHW Post-Circulation Time
0…199
Sec
1
0
PAR
39 Anti-legionella Function (Only hot water tank)
0 = Disabled
1 = Enabled
-
-
0
EXPANSION BOARD
PAR
40 No. of expansion boards
0….3
-
1
0
PAR
41 Mix Valve Motion Time
0 .. 199
10 sec
1
12
PAR
42 DHW Priority on Mixed Zone
0 = Parallel
1 = Absolute
-
-
1
PAR
43 Screed Drying
0 = Off
1 = Curve A
2 = Curve B
3 = Curve A+B
-
-
0
PAR
44 Solar thermal system type
1….8
--
1
1
PAR
45 ∆ton Solar Pump Manifold 1
P1
….50
°C
1
8
PAR
46 Delay to solar integration
“- -“, 0….199
min
1
0
PAR
47 Tmin Solar Manifold
“- -“, -30….0
°C
1
-10
PAR
48 Tmax Solar Manifold
“- -“, 80….199
°C
1
120
RESET
PAR
49 Reset default parameters (Par 01 – Par 02 equal
to “—”)
- , 1
-
-
-
6.5
Fault/error message
In the event of a fault/malfunction the message
"ALL"
will
appear on the display with the alarm number and the light bar
(4) will turn red.
Example: “ALL 02” (Low System Pressure Error: less than 0.8
bar).
Before repairing the fault:
– disconnect the appliance from the mains power by setting the
main switch to "OFF"
OFF
Fig. 31
– as a precautionary measure, close the gas isolation valve.
Repair the fault and start-up the boiler again.